Omron E5AN Communications Manual page 57

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Varia-
Ad-
Parameter name
ble type
dress
C3 (83)
000D
Alarm 1 Type
C3 (83)
000E
Alarm 2 Type
C3 (83)
000F
Alarm 3 Type (See note 1.)
C3 (83)
0010
Communications Unit No.
(See note 2.)
C3 (83)
0011
Communications Baud
Rate (See note 2.)
C3 (83)
0012
Communications Data
Length (See note 2.)
C3 (83)
0013
Communications Stop Bits
(See note 2.)
C3 (83)
0014
Communications Parity
(See note 2.)
C3 (83)
0015
Number of Multi-SP Uses
Note:
The alarm function can also be used in Controllers without alarm output terminals. In this case,
confirm alarm occurrences via the status data.
Note 1: Not displayed on the Controller display when Alarm 3 is not assigned to the output.
Note 2: After communications parameters have been changed, reset the Controller to enable them.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0):
Alarm function OFF
H'00000001 (1):
Upper and lower-limit alarm
H'00000002 (2):
Upper-limit alarm
H'00000003 (3):
Lower-limit alarm
H'00000004 (4):
Upper and lower-limit range alarm
H'00000005 (5):
Upper and lower-limit alarm with standby
sequence
H'00000006 (6):
Upper-limit alarm with standby sequence
H'00000007 (7):
Lower-limit alarm with standby sequence
H'00000008 (8):
Absolute-value upper-limit alarm
H'00000009 (9):
Absolute-value lower-limit alarm
H'0000000A (10):
Absolute-value upper-limit alarm with
standby sequence
H'0000000B (11):
Absolute-value lower-limit alarm with
standby sequence
H'0000000C (12):
LBA (Loop Burnout Alarm)
H'0000000D (13):
PV change rate alarm
H'00000000 (0):
Alarm function OFF
H'00000001 (1):
Upper and lower-limit alarm
H'00000002 (2):
Upper-limit alarm
H'00000003 (3):
Lower-limit alarm
H'00000004 (4):
Upper and lower-limit range alarm
H'00000005 (5):
Upper and lower-limit alarm with standby
sequence
H'00000006 (6):
Upper-limit alarm with standby sequence
H'00000007 (7):
Lower-limit alarm with standby sequence
H'00000008 (8):
Absolute-value upper-limit alarm
H'00000009 (9):
Absolute-value lower-limit alarm
H'0000000A (10):
Absolute-value upper-limit alarm with
standby sequence
H'0000000B (11):
Absolute-value lower-limit alarm with
standby sequence
H'0000000C (12):
No alarm function
H'0000000D (13):
PV change rate alarm
Same settings as the alarm 2 type
H'00000000 to H'00000063 (0 to 99)
H'00000000 (0): 1.2
H'00000001 (1): 2.4
H'00000002 (2): 4.8
H'00000003 (3): 9.6
H'00000004 (4): 19.2
H'00000005 (5): 38.4
H'00000006 (6): 57.6
H'00000007 (7): 7
H'00000008 (8): 8
H'00000001 (1): 1
H'00000002 (2): 2
H'00000000 (0): None
H'00000001 (1): Even
H'00000002 (2): Odd
H'00000000 (0): No multi-SP
H'00000001 (1): 2SP
H'00000002 (2): 4SP
Level
Initial set-
ting
Communi-
cations
setting
Initial set-
ting
3-7

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5gnE5enE5cn

Table of Contents