Omron E5AN Communications Manual page 55

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Variable
Ad-
Parameter name
type
dress
C1 (81)
0028
Move to Protect Level
C1 (81)
0029
Password to Move to Pro-
tect Level
C1 (81)
002A
Parameter Mask Enable
C1 (81)
002B
PF Key Protect
C1 (81)
002C
MV Change Rate Limit
C1 (81)
002F
Heater Overcurrent Detec-
tion 1
C1 (81)
0030
Heater Overcurrent Detec-
tion 2
C1 (81)
0031
Extraction of Square Root
Low-cut Point
C3 (83)
0000
Input Type
(Controllers with TC/Pt
universal input) (See note.)
Note:
The input type can be selected to match the connected sensor.
There are two input type specifications: Thermocouple/Resistance thermometer input and Analog
input.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
(Can only be set. The monitor value is always H'00000000.)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 to H'000003E8 (0.0 to 100.0)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'000001F4 (0.0 to 50.0)
H'00000000 to H'000003E8 (0.0 to 100.0)
H'00000000 (0):
Pt (−200 to 850°C/−300 to 1500°F)
H'00000001 (1):
Pt (−199.9 to 500.0°C/−199.9 to 900.0°F)
H'00000002 (2):
Pt (0.0 to 100.0°C/0.0 to 210.0°F)
H'00000003 (3):
JPt (−199.9 to 500.0°C/−199.9 to 900.0°F)
H'00000004 (4):
JPt (0.0 to 100.0°C/0.0 to 210.0°F)
H'00000005 (5):
K (−200 to 1300°C/−300 to 2300°F)
H'00000006 (6):
K (−20.0 to 500.0°C/0.0 to 900.0°F)
H'00000007 (7):
J (−100 to 850°C/−100 to 1500°F)
H'00000008 (8):
J (−20.0 to 400.0°C/0.0 to 750.0°F)
H'00000009 (9):
T (−200 to 400°C/−300 to 700°F)
H'0000000A (10):
T (−199.9 to 400.0°C/−199.9 to 700.0°F)
H'0000000B (11):
E (−200 to 600°C/−300 to 1100°F)
H'0000000C (12): L (−100 to 850°C/−100 to 1500°F)
H'0000000D (13): U (−200 to 400°C/−300 to 700°F)
H'0000000E (14):
U (−199.9 to 400.0°C/−199.9 to 700.0°F)
H'0000000F (15):
N (−200 to 1300°C/−300 to 2300°F)
H'00000010 (16):
R (0 to 1700°C/0 to 3000°F)
H'00000011 (17):
S (0 to 1700°C/0 to 3000°F)
H'00000012 (18):
B (100 to 1800°C/300 to 3200°F)
H'00000013 (19):
Infrared temperature sensor
(K 140°F/60°C)
H'00000014 (20):
Infrared temperature sensor
(K 240°F/120°C)
H'00000015 (21):
Infrared temperature sensor
(K 280°F/140°C)
H'00000016 (22):
Infrared temperature sensor
(K 440°F/220°C)
H'00000017 (23):
0 to 50 mV
H'00000018 (24):
W (0 to 2300°C/0 to 3200°F)
H'00000019 (25):
PL II (0 to 1300°C/0 to 2300°F)
Level
Protect
Adjustment
Initial set-
ting
3-5

Advertisement

Table of Contents
loading

This manual is also suitable for:

E5gnE5enE5cn

Table of Contents