Omron E5AN Communications Manual page 58

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

SECTION 3 Communications Data for CompoWay/F and SYSWAY
Vari-
Ad-
able
Parameter name
dress
type
C3 (83)
0016
Event Input Assignment 1
(See note 1.)
C3 (83)
0017
Event Input Assignment 2
(See note 2.)
C3 (83)
0018
Event Input Assignment 3
C3 (83)
0019
Event Input Assignment 4
C3 (83)
001A
Multi-SP Uses
C3 (83)
001B
SP Ramp Time Unit
C3 (83)
001C
SP Ramp Set Value
C3 (83)
001D
Standby Sequence Reset
C3 (83)
001E
Auxiliary Output 1 Open in
Alarm
C3 (83)
001F
Alarm 1 Hysteresis
Note 1: For Controllers with two event inputs (events 1 and 2), this cannot be set if the Number of Multi-SP
Uses parameter is set to 1 or 2.
Note 2: For Controllers with two event inputs (events 1 and 2), this cannot be set if the Number of Multi-SP
Uses parameter is set to 2.
Note 3: PRST (program start) can be set even when the program pattern is set to OFF, but the function
will be disabled.
3-8
Setting (monitor) value
H'00000000 (0):
None
H'00000001 (1):
RUN/STOP
H'00000002 (2):
Auto/manual switch
H'00000003 (3):
Program Start (See note 3.)
H'00000004 (4):
Direct/reverse operation
H'00000005 (5):
None
H'00000006 (6):
100% AT execute/cancel
H'00000007 (7):
40% AT execute/cancel
H'00000008 (8):
Setting change enable/disable
H'00000009 (9):
Communications writing enable/disable
H'0000000A (10):
Alarm latch cancel
H'00000000 to H'0000000A (0 to 10)
* Same as for Event Input Assignment 1.
H'00000000 to H'0000000A (0 to 10)
* Same as for Event Input Assignment 1.
H'00000000 to H'0000000A (0 to 10)
* Same as for Event Input Assignment 1.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): EU/second
H'00000001 (1): EU/minute
H'00000002 (2): EU/hour
H'00000000 (0): OFF
H'00000001 to H'0000270F (1 to 9999)
H'00000000 (0): Condition A
H'00000001 (1): Condition B
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt universal input models)
(0.01 to 99.99 for Analog input models)
Level
Initial set-
ting
Advanced
function
setting
Adjust-
ment
Advanced
function
setting
Initial set-
ting