Omron E5AN Communications Manual page 53

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Variable
Ad-
Parameter name
type
dress
C1 (81)
0000
Operation/Adjustment Pro-
tect
C1 (81)
0001
Initial Setting/Communica-
tions Protect
C1 (81)
0002
Setting Change Protect
C1 (81)
0003
Set Point
C1 (81)
0004
Alarm Value 1
C1 (81)
0005
Alarm Value Upper Limit 1
C1 (81)
0006
Alarm Value Lower Limit 1
C1 (81)
0007
Alarm Value 2
C1 (81)
0008
Alarm Value Upper Limit 2
C1 (81)
0009
Alarm Value Lower Limit 2
C1 (81)
000A
Alarm Value 3 (See note 1.)
C1 (81)
000B
Alarm Value Upper Limit 3
(See note 1.)
C1 (81)
000C
Alarm Value Lower Limit 3
(See note 1.)
C1 (81)
000D
Heater Burnout Detection 1
C1 (81)
000E
SP 0
C1 (81)
000F
SP 1
C1 (81)
0010
SP 2
C1 (81)
0011
SP 3
C1 (81)
0012
Temperature Input Shift
C1 (81)
0013
Upper Limit Temperature
Input Shift Value
C1 (81)
0014
Lower Limit Temperature
Input Shift Value
Note:
The alarm function can also be used in Controllers without alarm output terminals. In this case,
confirm alarm occurrences via the status data.
Note 1: Not displayed on the Controller display when Alarm 3 is not assigned to an output.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0):
No restrictions in operation and adjust-
ment levels
H'00000001 (1):
Move to adjustment level is prohibited.
H'00000002 (2):
Display and change of only "PV" and
"PV/SP" parameters is allowed.
H'00000003 (3):
Display of only "PV" and "PV/SP" parame-
ters is allowed.
H'00000000 (0):
Move to initial setting/communications
setting level is allowed. (Move to
advanced function setting level is dis-
played.)
H'00000001 (1):
Move to initial setting/communications
setting level is allowed. (Move to
advanced function setting level is not dis-
played.)
H'00000002 (2):
Move to initial setting/communications
setting level is prohibited.
H'00000000 (0):
OFF (Changing of setup on Controller dis-
play is allowed.)
H'00000001 (1):
ON (Changing of setup on Controller dis-
play is prohibited.)
SP lower limit to SP upper limit
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'FFFFF831 to H'0000270F (−1999 to 9999)
H'00000000 to H'000001F4 (0.0 to 50.0)
SP lower limit to SP upper limit
SP lower limit to SP upper limit
SP lower limit to SP upper limit
SP lower limit to SP upper limit
H'FFFFF831 to H'0000270F (−199.9 to 999.9)
H'FFFFF831 to H'0000270F (−199.9 to 999.9)
H'FFFFF831 to H'0000270F (−199.9 to 999.9)
Level
Protect
Operation
Adjustment
3-3