SECTION 3 Communications Data for CompoWay/F and SYSWAY
Vari-
Ad-
able
Parameter name
dress
type
C3 (83)
0050
Auxiliary Output 1
Assignment
C3 (83)
0051
Auxiliary Output 2
Assignment
C3 (83)
0052
Character Select
C3 (83)
0053
Program Pattern
C3 (83)
0054
Soak Time Unit
C3 (83)
0055
Alarm SP Selection
C3 (83)
0056
Auxiliary Output 3
Assignment
C3 (83)
005B
Manual MV Limit Enable
C3 (83)
005D
AT Calculated Gain
C3 (83)
005E
AT Hysteresis
C3 (83)
005F
Limit Cycle MV Ampli-
tude
C3 (83)
0067
PV Rate of Change Cal-
culation Period
C3 (83)
0068
Automatic Cooling Coef-
ficient Adjustment
C3 (83)
0069
Heater Overcurrent Use
C3 (83)
006A
Heater Overcurrent
Latch
C3 (83)
006B
Heater Overcurrent Hys-
teresis
Note 1: P.END (program end output) can be set even when the program pattern is set to OFF, but the
function will be disabled.
Note 2: The output turns ON when the status of either the Control Output 1 ON/OFF Count Alarm or the
Control Output 2 ON/OFF Count Alarm turns ON.
3-12
Setting (monitor) value
H'00000000 (0): Not assigned.
H'00000001 (1): Control output (heating)
H'00000002 (2): Control output (cooling)
H'00000003 (3): Alarm 1
H'00000004 (4): Alarm 2
H'00000005 (5): Alarm 3
H'00000006 (6): Program end output (See note 1.)
H'00000007 (7): Control output ON/OFF count alarm (See note 2.)
H'00000008 (8): Work bit 1
H'00000009 (9): Work bit 2
H'0000000A (10): Work bit 3
H'0000000B (11): Work bit 4
H'0000000C (12): Work bit 5
H'0000000D (13): Work bit 6
H'0000000E (14): Work bit 7
H'0000000F (15): Work bit 8
H'00000000 to H'0000000F (0 to 15)
* Same as for the Auxiliary Output 1 Assignment parameter.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): STOP
H'00000002 (2): CONT
H'00000000 (0): Minutes
H'00000001 (1): Hours
H'00000000 (0): Set point during SP ramp
H'00000001 (1): Set point
H'00000000 to H'0000000F (0 to 15)
* Same as for the Auxiliary Output 1 Assignment parameter.
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'00000064 (0.1 to 10.0)
H'00000001 to H'0000270F (0.1 to 999.9: Controllers with TC/Pt
universal input)
(0.01 to 9.99: Controllers with analog input)
H'00000032 to H'000001F4 (5.0 to 50.0)
H'00000001 to H'000003E7 (1 to 999)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000001F4 (0.1 to 50.0)
Level
Advanced
function
setting
Initial set-
ting
Advanced
function
setting

Advertisement