Omron E5AN Communications Manual page 59

Digital temperature controllers
Hide thumbs Also See for E5AN:
Table of Contents

Advertisement

Variable
Ad-
Parameter name
type
dress
C3 (83)
0020
Auxiliary Output 2 Open in
Alarm
C3 (83)
0021
Alarm 2 Hysteresis
C3 (83)
0022
Auxiliary Output 3 Open in
Alarm (See note 1.)
C3 (83)
0023
Alarm 3 Hysteresis
(See note 1.)
C3 (83)
0024
HB ON/OFF
C3 (83)
0025
Heater Burnout Latch
C3 (83)
0026
Heater Burnout Hysteresis
C3 (83)
0027
ST Stable Range
α
C3 (83)
0028
C3 (83)
0029
MV Upper Limit
C3 (83)
002A
MV Lower Limit
C3 (83)
002B
Input Digital Filter
C3 (83)
002C
Additional PV Display
C3 (83)
002D
MV Display
C3 (83)
002E
Automatic Display Return
Time
C3 (83)
002F
Alarm 1 Latch
C3 (83)
0030
Alarm 2 Latch
C3 (83)
0031
Alarm 3 Latch (See note 1.)
C3 (83)
0032
Move to Protect Level Time
C3 (83)
0033
Input Error Output
C3 (83)
0034
Cold Junction Compensa-
tion Method
C3 (83)
0035
MB Command Logic
Switching (See note 2.)
Note:
The alarm function can also be used in Controllers without alarm output terminals. In this case,
confirm alarm occurrences via the status data.
Note 1: Not displayed on the Controller display when Alarm 3 is not assigned to the output.
Note 2: The logic is switched only in the MB command (SYSWAY). The logic of CompoWay/F operation
command code 00 (communications writing) is not affected.
3.1 Variable Area (Setting Range) List
Setting (monitor) value
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt universal input models)
(0.01 to 99.99 for Analog input models)
H'00000000 (0): Close in alarm
H'00000001 (1): Open in alarm
H'00000001 to H'0000270F
(0.1 to 999.9 for TC/Pt universal input models)
(0.01 to 99.99 for Analog input models)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'000001F4 (0.1 to 50.0)
H'00000001 to H'0000270F (0.1 to 999.9)
H'00000000 to H'00000064 (0.00 to 1.00)
Standard: MV lower limit + 0.1 to H'0000041A (MV lower limit +
0.1 to 105.0)
Heating and cooling: H'00000000 to H'0000041A (0.0 to 105.0)
Standard: H'FFFFFFCE to MV upper limit − 0.1 (−5.0 to MV upper
limit − 0.1)
Heating and cooling: H'FFFFFBE6 to H'00000000 (−105.0 to 0.0)
H'00000000 to H'0000270F (0.0 to 999.9)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF (display of manipulated variable OFF)
H'00000001 (1): ON (display of manipulated variable ON)
H'00000000 (0): OFF
H'00000001 to H'00000063 (1 to 99)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000001 to H'0000001E (1 to 30)
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
H'00000000 (0): OFF
H'00000001 (1): ON
Level
Advanced
function
setting
Initial set-
ting
Advanced
function
setting
Initial set-
ting
Advanced
function
setting
Adjust-
ment
Advanced
function
setting
3-9