Troubleshooting by Remote Controller
2.9

Electronic Expansion Valve Coil Abnormality (Y1E~Y3E)

E9
Remote
Controller
Display
Applicable
RQYQ-PY1B
Models
Method of Error
Check the continuity of electronic expansion valve coil (Y1E)
Detection
Error Decision
No current is detected in the common (COM [+]) when power supply is ON.
Conditions
Supposed
Causes
116
Disconnection of connectors for electronic expansion valve (Y1E)
Defective electronic expansion valve coil
Defective outdoor unit main PCB (A1P)