Troubleshooting by Remote Controller
2.9
Electronic Expansion Valve Coil Abnormality (Y1E~Y3E)
E9
Remote
Controller
Display
Applicable
RQYQ-PY1B
Models
Method of Error
Check the continuity of electronic expansion valve coil (Y1E)
Detection
Error Decision
No current is detected in the common (COM [+]) when power supply is ON.
Conditions
Supposed
Causes
116
Disconnection of connectors for electronic expansion valve (Y1E)
Defective electronic expansion valve coil
Defective outdoor unit main PCB (A1P)
SiBE341027
Service Diagnosis