Wiring To Control Terminals - Danfoss 102 Operating Instructions Manual

Hvac drive 1.1-90 kw
Table of Contents

Advertisement

Installation
Also provided are two Form C relay outputs that
are in various locations depending upon the
frequency converter configuration and size
Some options available for ordering with the unit
may provide additional terminals. See the manual
2
2
provided with the equipment option.
See 10.2 General Technical Data for terminal ratings details.
Terminal Parameter
12, 13
18
19
32
33
27
29
20
37
39
42
50
53
54
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
18
VLT
Terminal Description
Digital Inputs/Outputs
Default
Setting
Description
-
+24 V DC
24 V DC supply
voltage. Maximum
output current is 200
mA total for all 24 V
loads. Useable for
digital inputs and
external transducers.
5-10
[8] Start
5-11
[0] No
operation
5-14
[0] No
Digital inputs.
operation
5-15
[0] No
operation
5-12
[2] Coast
Selectable for digital
inverse
input and output.
Default setting is
5-13
[14] JOG
input.
-
Common for digital
inputs and 0 V
potential for 24 V
supply.
-
Safe Torque
(optional) Safe input.
Off (STO)
Used for STO
Analog Inputs/Outputs
-
Common for analog
output
6-50
Speed 0 -
Programmable analog
High Limit
output. The analog
signal is 0-20 mA or
4-20 mA at a
maximum of 500 Ω
-
+10 V DC
10 V DC analog
supply voltage. 15 mA
maximum commonly
used for potenti-
ometer or thermistor.
6-1
Reference
Analog input.
Selectable for voltage
6-2
Feedback
or current. Switches
A53 and A54 select
mA or V.
MG11AI02 - VLT
®
HVAC Drive Operating Instructions
Terminal Parameter
55
61
68 (+)
69 (-)
01, 02, 03
04, 05, 06
Table 2.4 Terminal Description

2.4.5.3 Wiring to Control Terminals

Control terminal connectors can be unplugged from the
frequency converter for ease of installation, as shown in
Illustration 2.20.
Illustration 2.20 Unplugging Control Terminals
1.
Open the contact by inserting a small screwdriver
into the slot above or below the contact, as
shown in Illustration 2.21.
2.
Insert the bared control wire into the contact.
3.
Remove the screwdriver to fasten the control wire
into the contact.
4.
Ensure the contact is firmly established and not
loose. Loose control wiring can be the source of
equipment faults or less than optimal operation.
See 10.1 Power-dependent Specifications for control terminal
wiring sizes.
®
is a registered Danfoss trademark
Terminal Description
Digital Inputs/Outputs
Default
Setting
Description
-
Common for analog
input
Serial Communication
-
Integrated RC-Filter
for cable screen. ONLY
for connecting the
screen when experi-
encing EMC problems.
8-3
RS-485 Interface. A
control card switch is
8-3
provided for
termination resistance.
Relays
5-40 [0]
[0] Alarm
Form C relay output.
Usable for AC or DC
5-40 [1]
[0] Running
voltage and resistive
or inductive loads.