Danfoss 102 Operating Instructions Manual page 57

Hvac drive 1.1-90 kw
Table of Contents

Advertisement

Status Messages
QStop
The motor is decelerating using 3-81 Quick
Stop Ramp Time.
Quick stop inverse was chosen as a function
for a digital input (parameter group 5-1*).
The corresponding terminal is not active.
The quick stop function was activated via
serial communication.
Ramping
The motor is accelerating/decelerating using
the active Ramp Up/Down. The reference, a
limit value or a standstill is not yet reached.
Ref. high
The sum of all active references is above the
reference limit set in 4-55 Warning Reference
High.
Ref. low
The sum of all active references is below the
reference limit set in 4-54 Warning Reference
Low.
Run on ref.
The frequency converter is running in the
reference range. The feedback value matches
the setpoint value.
Run request
A start command has been given, but the
motor is stopped until a run permissive signal
is received via digital input.
Running
The frequency converter runs the motor.
Sleep Mode
The energy saving function is enabled. The
motor has stopped, but will restart automat-
ically when required.
Speed high
Motor speed is above the value set in
4-53 Warning Speed High.
Speed low
Motor speed is below the value set in
4-52 Warning Speed Low.
Standby
In Auto On Auto mode, the frequency
converter starts the motor with a start signal
from a digital input or serial communication.
Start delay
In 1-71 Start Delay, a delay starting time was
set. A start command is activated and the
motor will start after the start delay time
expires.
Start fwd/rev
Start forward and start reverse were selected
as functions for two different digital inputs
(parameter group 5-1* Digital Inputs). The
motor starts in forward or reverse depending
on which corresponding terminal is activated.
Stop
The frequency converter has received a stop
command from the LCP, digital input or serial
communication.
Trip
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, the
frequency converter can be reset manually by
pressing [Reset] or remotely by control
terminals or serial communication.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
®
VLT
HVAC Drive Operating Instructions
Operation Status
®
MG11AI02 - VLT
is a registered Danfoss trademark
Operation Status
Trip lock
An alarm occurred and the motor is stopped.
Once the cause of the alarm is cleared, power
must be cycled to the frequency converter.
The frequency converter can then be reset
manually by pressing [Reset] or remotely by
control terminals or serial communication.
Table 7.3 Status Message Operation Status