Reverting Ui Modes - KMC Controls FlexStat Application Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat:
Table of Contents

Advertisement

Reverting UI Modes

Via the User Interface
Reverting to Standard mode can be done through the FlexStat's user
interface with a combination of button presses or by changing MSV9's
values through BACstage or TotalControl. To revert to Standard mode
through the user interface, follow these steps to access the hidden
menus:
1. Press and hold both the Enter and Right buttons for at least five sec-
onds. (If you push the Right button before Enter while in Hospitality
mode, you will go to the Field B screen.)
2. While continuing to hold those two buttons, press the Left button and
hold all three buttons for at least five seconds.
3. Release the Right button but continue holding the Left and Enter but-
tons until the FlexStat menu appears (after about five more seconds).
NOTE: While holding the Left, Right, and/or Enter buttons, do not
accidentally also hold the Up or Down button.
NOTE: The FlexStat menu has view-only About, Date, and Time
lines. The About selection contains the same information as
the About screen in the Standard mode's Main Menu. The
Date and Time lines simply display the current date and time
information.
4. To access and make changes in the "hidden" Main Menu, use the
Up/Down buttons to navigate to the SECOND blank line below the
Time line and press the Enter button.
NOTE: Access to this hidden menu is password protected (if both the
Operator and Administrator passwords are not 0000). Entering
either an Operator or Administrator level password accesses
the Main menu (a User password will not work).
5. The menus operate as normal from this point. To return to Standard
mode, navigate to the Advanced > User Interface menu and select
Standard (otherwise, the previously selected mode will continue).
FlexStat (General)
Via BACstage or TotalControl
To revert to Standard mode through BACstage or TotalControl:
1. Change the Present Value of MSV9 from 2 (HOSPITALITY in
TotalControl) or 3 (LOCKED UI) to 1 (STANDARD).
NOTE: When the FlexStat is restarted, however, MSV9's Present
Value will revert to the Relinquished Default and the user
interface will revert to the previously selected mode. If a
quick configuration change is desired instead of a permanent
mode change, this is a helpful tool.
2. To make the change permanent, change the Present Value AND the
Relinquished Default to the desired value.
NOTE: Do not change the Present Values or Relinquished Defaults
of any other MSVs 1–12. Doing so may make the FlexStat
malfunction!
19