Bac-1Xxx53 Series (5 Relays, 1 Triac, & 3 Analog Outputs) - KMC Controls FlexStat Application Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat:
Table of Contents

Advertisement

(5 Relays, 1 Triac, & 3 Analog Outputs)
The BAC-120053CW FlexStat is a 5-relay, 1-triac,
and 3-analog-output controller with special firm-
ware that is used to control the Copeland Scroll
Digital
compressor. (See
www.EmersonClimate.
com.) The BAC-120053CW is similar to the Emer-
son 543-0175-00 Commercial Comfort Controller
(which is manufactured exclusively for the Cope-
land Scroll Digital compressor by KMC Controls as
a customized version of KMC's standard FlexStat).
The BAC-120053CW has a KMC logo (instead of
Emerson), plus economizer and (with a remote
CO
sensor) Demand Control Ventilation (DCV)
2
functionality.
The triac replaces Relay 6 and is used to modu-
late the compressor. HPU and RTU applications (only) are supported.
Other specifications are the same as for the BAC-120063C model (see
also the
BAC-12xxxx/13xxxx/14xxxx Series FlexStat Data
In single compressor applications, the FlexStat varies the capacity of
the Scroll Digital compressor over 10–100% of the rated capacity. Below
10% cooling demand, the FlexStat controls at 10% to meet low levels
of demand. In multiple compressor (tandem) applications, the FlexStat
manages the variable capacity Scroll Digital compressor as the 1st stage
of cooling, effectively providing 5–100% variable capacity control over
the full range of cooling demand in a multiple compressor (tandem) ap-
plication.
BAC-1xxx53 Series (5 Relays, 1 Triac, and 3 Analog Outputs) Section
BAC-1xxx53 Series
For a general bill of material items and general HPU and RTU sequence
of operations, see
puts) on page
®
Note:
Sheet).
58
BAC-1xx63/1xxx63 Series (6 Relays and 3 Analog Out-
27.
Expected availability of this model is the third quarter of 2012.
When available, see the BAC-1xx53 Installation Guide section
for detailed drawings and input/output connections as well as
other important installation information.
NOTE: SC = Switched
(relay) Common
NOTE: IN1 and IN5–6 are
reserved for internal sensors
IN9
Inputs
(DTS) IN8
GND
(Remote Temp.) IN7
+B
(Optional)
MS/TP Network
–A
IN4
Inputs
IN3
(Wiring is dependent
on application)
GND
(FST/DAT) IN2
Common/–/C
24 VAC
Phase/ /R
(Optional)
IP/Ethernet
Network
Outputs (HPU | RTU)
Analog 9
GND 7–9
Analog 8
Analog 7
Triac 6 (T | T)
SC 4–6 (R | R/RH)
Relay 5 (W | W1)
Relay 4 (Y2 | Y2)
Relay 3
(Y1 | Y1)
SC 1–3
(R | R/RC)
Relay 2
(O/B | W2)
Relay 1
(G | G)
Application Guide L