Hospitality And Locked User Interface Modes; Selecting Ui Modes - KMC Controls FlexStat Application Manual

Bacnet programmable thermostats
Hide thumbs Also See for FlexStat:
Table of Contents

Advertisement

Hospitality and Locked User Interface Modes

Selecting UI Modes

USER INTERFACE
MODE:
STANDARD
ROTATION VALUES
SHOW TEMP TENTHS: NO
Advanced > User Interface toggles the home screen and other menus
between the default Standard mode and other (more restricted) modes.
NOTE: COMPLETE ALL OTHER NECESSARY CONFIGURATION
BEFORE SELECTING HOSPITALITY OR LOCKED UI
MODE! After Hospitality or Locked UI mode is selected, it is
intentionally difficult to revert to Standard mode!
NOTE: As additional security against unauthorized bypass of
Hospitality or Locked UI mode from the FlexStat, set at least
an Operator level password. (See the
Guide.)
Locked UI mode (also known as Mode 3) on the Home screen, but all
button functions (except the backlight) are locked.
Hospitality mode (also known as Mode 2) has limited menus and is typ-
ically used in hotel rooms. Users typically can change only the setpoint,
system mode, and fan speed. Pushing the Left and Right buttons displays
customizable menu selections (dependent on the configuration), such
as System (Auto, Heat, Cool, and Off) and Fan (Auto, High, Medium).
(See the
FlexStat Operation Guide
options.)
NOTE: Menus depend on the configured options. A three-speed fan
will display Auto, Low, Medium, and High, but a one-speed
fan will only display Auto and On.
NOTE: Auto in System Mode does not currently have an icon
implemented with it. Manually selecting Heat or Cool will
display an icon on the Home screen.
FlexStat (General)
USER INTERFACE
MODE:
HOSPITALITY
ROTATION VALUES
HOSPITALITY OPTIONS
SETPT CNTRL: SINGLE
FlexStat Operation
about Single Setpoint vs. Schedule
NOTE: If this new feature does not work (is "Inactive") after
upgrading the firmware (especially from R1.3.0.4 or earlier),
you may need to restore the factory default (especially if there
is custom programming or configuration in the FlexStat) and
reconfigure the FlexStat. See the
information.
(Hospitality Mode Sample Screens)
WED 10/01
3:20 PM
COOL
HIGH
WELCOME
HUM: 46% RH
Pushing Enter Button Toggles
Pushing Left Button Goes to Field A Screen
SYSTEM MODE
AUTO
HEAT
COOL
OFF
Custom Hospitality mode programming is required for:
• Use of Field C for displaying messages.
• Creating additional/alternate menu options.
• Any use of AHU or RTU applications in firmware R1.3.0.11. (Firm-
ware earlier than R1.3.0.11 did not support Hospitality mode at all,
and R1.3.0.11 natively supported only FCU or HPU applications in
Hospitality mode. The latest firmware supports all the applications.)
See
Programming Custom Text for Hospitality Mode on page 21
tom Programming on page
8.
18
FlexStat Operation Guide
(Field A Selection)
(Field B Selection)
(Optional Programmed Field C Message)
(Rotation Value)
°F/°C Temperature Scale
(Pushing Right
Button Goes to
Field B Screen)
(No Field C Screen Exists)
Application Guide, Rev L