Viessmann VITOCAL 200-G Installation And Service Instructions Manual page 8

Type bwc & bwc-m 201.a06 to a17, 6 to 17 kw single stage heat pump with electric drive, 400 v~ & type bwc-m 201.a06 to a10, 6 to 10 kw single stage heat pump with electric drive, 230 v~
Table of Contents

Advertisement

Preparing for installation
Siting
(cont.)
■ To prevent structure-borne noise,
never site the appliance on ceilings
with wooden joists (e.g. in the attic).
■ Level the appliance horizontally.
If the adjustable feet are used to com-
pensate for an uneven floor (max.
10 mm), the pressure load on the feet
must be distributed evenly.
Type BWC 201.A,
Type BWC-M 201.A
06
08
10
13
17
■ Observe required minimum clearan-
ces:
8
■ Observe the required floor area and
minimum room volume (to
DIN EN 378).
Refrigerant volume
1.2 kg
1.45 kg
1.7 kg
2.2 kg
2.9 kg
B
A ■ With hydraulic module (acces-
sory, for installation above the
heat pump):
340 mm
■ Without hydraulic module:
Subject to on-site installation and
site conditions
B ≥ 100 mm
Min. space require-
ment
2.73 m
3
3
3.30 m
3
3.86 m
5.00 m
3
3
6.59 m
A
≥ 400