Electrical connections
Controller and sensor PCB
Set the required parameters during com-
missioning; see from page 66.
Sensors
Plug
Sensor
F0
Outside temperature sensor; connect on site
F4
Buffer temperature sensor, top; connect on site
(X5.6/X5.7)
F6
Cylinder temperature sensor, top; connect on
(X6.1/X6.2)
site
F7
Cylinder temperature sensor, bottom; connect on
(X6.1/X6.3)
site
F13
Flow temperature sensor, system (with sensor
well, downstream of heating water buffer cylin-
der); connect on site
F14
Flow temperature sensor, cooling circuit (direct
heating circuit A1 or separate cooling circuit);
connect on site
F16
Room temperature sensor for separate cooling
circuit (required) or for direct heating/cooling cir-
cuit (recommended); connect on site
F20
Boiler water temperature sensor, external heat
(X6.8/X6.9)
generator; connect on site
aVG
KM BUS
Connection of components on site (cores inter-
changeable). Use the KM BUS distributor (ac-
cessory) if several of the following devices are
connected.
■ Extension kit for one heating circuit with mixer
M2
■ Vitotrol 200A remote control (assign the heat-
ing circuits at the remote control)
■ External H1 extension
■ Vitocom 100 communication interface
■ Vitosolic 100/200 solar control units
(cont.)
Note
■ Plug F11, F17:
On site, connect nothing to plug F11
and F17.
Installation sequence
Type
Ni500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Pt500
(PTC)
Ni500
(PTC)
Ni500
(PTC)
Pt500
(PTC)
51