Further details regarding the individual steps
Checking the refrigerant circuit for leaks
1. Check the floor area, valves and all
visible solder joints for traces of oil.
Note
Traces of oil indicate a leaking refrig-
erant circuit. Have your heat pump
checked over by a refrigeration engi-
neer.
Charging and venting the primary side
!
Please note
To prevent equipment damage,
fill the primary circuit before con-
necting the power supply.
1. Check the pre-charge pressure of the
expansion vessel.
2. Fill the primary circuit with
Viessmann heat transfer medium
and vent.
Note
The system must be protected
against frost down to –15 °C.
Viessmann heat transfer medium is a
ready-mixed ethylene glycol-based
medium, for down to –15 °C, contain-
ing inhibitors for corrosion protec-
tion.
Charging and venting the secondary side
!
Please note
To prevent appliance damage,
protect electrical components
mounted on the casing door from
escaping liquids.
Commissioning, inspection, maintenance
(cont.)
2. Check the heat pump interior with a
refrigerant leak detector or leak
detecting spray for refrigerant leaks.
3. Check the connections for possible
leaks. Replace faulty or displaced
gaskets.
Note
Before filling the system, observe
VDI 2035 part 1.
1. Open any on-site non-return valves if
installed.