Page 1
45, 60 and 80 VITODENS 200-W Product may not be exactly as shown Vitodens 200-W Series B2HA, Models 19, 28, 35, 45, 60 and 80 Gas-Fired Wall-Mounted Condensing Boiler with modulating MatriX cylinder burner for room air independent operation (using a direct vent system) or room air dependent operation.
Product Information Vitodens 200-W, B2HA 19 to 80 Technical Data Vitodens 200-W Equipped with the industry’s first intelligent combustion management system and powerful control technology, the new generation Vitodens 200-W gas-fired wall-mount condensing boiler delivers unparalleled performance, reliability and comfort.
Product Information Vitodens 200-W, B2HA 19 to 80 Technical Data Cross-Section Vitodens 200-W B2HA 19, 28, 35, 45, 60, 80 A Inox-Radial heat exchanger made from stainless steel – for high operational reliability and a long service life. Large heating output in the smallest of spaces...
Technical Data Vitodens 200-W, B2HA 19 to 80 Technical Data Technical Data Boiler Model No. 200-W B2HA Natural Gas / Liquid Propane Gas CSA input 12-67 19-100 19-125 60-160 60-212 104-285 3.5-20 5.5-29 5.5-37 17.5-47 17.5-62 30-83 CSA output/DOE *1 10.9-61...
Page 5
Measured flue gas temperature with a combustion air temperature of 68° F (20° C). Based on maximum input rate. Requires 1 inch (25 mm) tubing. See the Installation Instructions of the Vitodens 200-W, B2HA for details. For side wall vent installations (coaxial system): Do not exceed max.
Page 6
Dimensional Information Vitodens 200-W, B2HA 19 to 80 Technical Data Models 200-W, B2HA 19, 28, 35 Legend Boiler Supply Condensate drain Combustion air intake (left or right) ¾ Gas Connection, ” NPTF Combustion air intake (through co-axial) Boiler Return Recommended height (single boiler system)
Page 7
Dimensional Information Vitodens 200-W, B2HA 19 to 80 Technical Data Models 200-W, B2HA 45, 60 Legend Boiler Supply Gas Connection, 1” NPTF Boiler Return Recommended height (single boiler system) Condensate drain...
Page 8
Dimensional Information Vitodens 200-W, B2HA 19 to 80 Technical Data Model B2HA 80 Legend Boiler Supply Gas Connection, 1” NPTF Boiler Return Recommended height (single boiler system) Condensate drain...
Minimum Clearances Vitodens 200-W, B2HA 19 to 80 Technical Data Recommended Minimum Service Clearances Minimum Clearances to Combustibles Front Rear Left Right Vent pipe *1 0 0 AL, CL AL= Alcove CL= Closet *1 Refer to the Installation Instructions of the Vitodens 200-W, B2HA Venting System for details.
Waterside Flow Vitodens 200-W, B2HA 19 to 80 Technical Data Waterside Flow (primary circuit) The Vitodens 200-W, B2HA is designed for closed loop, A low-loss header offers additional benefits not provided forced circulation hot water heating systems only. Use by a pair of closely spaced tees. Viessmann therefore standard friction loss method for pipe sizing.
Pump Information Vitodens 200-W, B2HA 19 to 80 Technical Data Heating Circuit / Boiler Pumps Viessmann offers a variety of Grundfos heating circuit/ Before using the following pumps for a DHW tank boiler pumps which meet typical Vitodens system application, find out the proper pressure drop through the installation requirements (see “Heating circuit pump...
Page 14
Low-Loss Header Information Vitodens 200-W, B2HA 19 to 80 Technical Data Low-Loss Header Application Sizing of Low-Loss Header in a Residential Single-Boiler Application Boiler No. of Boiler Typical System Flow Rates Viessmann Model Boilers Max. Low-loss Temp. Flow Sensor Rate...
Page 15
200/120 200/120 200/120 Note: for multiple boiler applications when using the Vitodens 200-W, B2HA boilers, refer to the multiple boiler low-loss distribution manifold installation instructions. *1 For system t < 20° F use low-loss header sizes for t 20° F.
Page 16
250/150 250/150 200/120 Note: for multiple boiler applications when using the Vitodens 200-W, B2HA boilers, refer to the multiple boiler low-loss distribution manifold installation instructions. *1 For system t < 20° F use low-loss header sizes for t 20° F.
Page 17
300/200 250/150 250/150 Note: for multiple boiler applications when using the Vitodens 200-W, B2HA boilers, refer to the multiple boiler low-loss distribution manifold installation instructions. *1 For system t < 20° F use low-loss header sizes for t 20° F.
DHW Production Vitodens 200-W, B2HA 19 to 80 Technical Data Domestic Hot Water Production Vitodens 200-W boilers can be used in conjunction For the connection of a stand-alone DHW tank, installation with the stand-alone DHW storage tanks offered by fittings (field supplied), an external circulating pump for Viessmann.
DHW Recirculation Vitodens 200-W, B2HA 19 to 80 Technical Data Domestic Hot Water Recirculation Vitocell-V stand-alone DHW storage tank DHW recirculation lines increase the level of comfort and convenience of the domestic hot water supply and reduce water consumption. These advantages directly derive from the immediate availability of domestic hot water at all draw points.
Wall Mounting Vitodens 200-W, B2HA 19 to 80 Technical Data Mounting Bracket Fitting the wall mounting bracket See the installation instructions applicable to the mounting bracket on each type of material. CAUTION Whichever mounting method is used, ensure that the bracket is tightly and securely fastened to wall.
Page 21
Wall Mounting Vitodens 200-W, B2HA 19 to 80 Technical Data Models B2HA 45, 60 1. Remove the external accessories connection box cover. 2. Loosen the screws at the bottom of the boiler (do not remove completely). 3. Remove the front encloser panel (lift up and pull away from the boiler).
Page 22
(recommended concrete expansion anchors are Hilti model KB-TZ e x 4 or equivalent. The Vitodens 200-W, model B2HA does not come with a mounting template. The wall location for the frame, mounting bracket and all vents must be field calculated.
Page 23
Frame Mounting Vitodens 200-W, B2HA 19 to 80 Technical Data Models B2HA 19, 28, 35 1. Remove the external accessories connection box cover. 2. Loosen the screws at the bottom of the boiler (do not remove completely). 3. Remove the front encloser panel (lift up and pull away from the boiler).
Page 24
Frame Mounting Vitodens 200-W, B2HA 19 to 80 Technical Data Model B2HA 80 1. Remove the external accessories connection box cover. 2. Loosen the screws at the bottom of the boiler (do not remove completely). 3. Remove the front encloser panel (lift up and pull away from the boiler).
It must be installed with a suitable gradient and provided with a stench trap. If the condensate outlet of the Vitodens 200-W boiler is lower than the drain, a condensate pump must be used. Only corrosion-resistant materials must be used for Condensate Connection for Vitodens condensate drainage purposes (e.g.
Venting Options/Electrical Connection/Control Vitodens 200-W, B2HA 19 to 80 Technical Data Venting Options For detailed information refer to the Installation Instructions for the Vitodens 200-W, B2HA Venting System. Vent Connection, (with optional Vent Connection, Vent Connection, air intake openings on sides)
Boiler Control Vitodens 200-W, B2HA 19 to 80 Technical Data On-Board Vitotronic 200, HO1B Control Modular structure Programming unit: Easy operation through: ■ The control unit is integrated into the boiler. The control – Plain text display with graphic ability unit comprises a standard unit, electronics modules and –...
Boiler Control Vitodens 200-W, B2HA 19 to 80 Technical Data Design and Function Functions Setting the Operating Programs The heating system frost protection (see Weather-compensated control of the boiler water ■ frost protection function) applies to all heating programs. and/or flow temperature...
Boiler Control Vitodens 200-W, B2HA 19 to 80 Technical Data Design and Functions (continued) Technical Data Heating Curve Adjustment (slope and shift) The control unit regulates the boiler water temperature Rated supply voltage: 120 VAC (= supply temperature of heating circuit without mixing...
Page 30
Accessories Vitodens 200-W, B2HA 19 to 80 Technical Data Design and Functions (continued) Boiler Temperature Sensor Outdoor Temperature Sensor The boiler temperature sensor is connected at the control unit for weather-responsive operation and is built into the boiler. Specification sensor type: Viessmann NTC 10K ohms at 77º...
Page 31
Accessories Vitodens 200-W, B2HA 19 to 80 Technical Data Vitotronic Control Accessories Supply Temperature Sensor Mixing Valve Actuator Kit (strap-on sensor, included with mixing valve actuator accessory kit), - when storing or transporting: -4 to+158° F (-20 to+70º C) The mixing valve actuator is mounted directly on the Viessmann ¾...
Page 32
Accessories Vitodens 200-W, B2HA 19 to 80 Technical Data Vitotronic Control Accessories (continued) Mixing Valve Extension Module KM BUS Expansion Module To connect 2 to 9 devices (mixing valve actuator, Vitotrol, input module, etc.) to the single KM BUS connection of the boiler.
Page 33
Accessories Vitodens 200-W, B2HA 19 to 80 Technical Data Vitotronic Control Accessories (continued) Vitotrol 200A One Vitotrol 200A can be used for every heating circuit Connection: in a heating system. The Vitotrol 200A can regulate one - 2-core lead, length max. 50 m (even if connecting...
Page 34
Accessories Vitodens 200-W, B2HA 19 to 80 Technical Data Vitotronic Control Accessories (continued) Vitotrol 300A One Vitotrol 300A can be used for every heating circuit RS function: in a heating system. The Vitotrol 300A can regulate up Installation in the main living room on an internal wall to three heating circuits.
Page 35
The temperature sensor connection [TS] typically located at the top of the low-loss header ensures low return temperatures to the Vitodens 200-W boiler at all times, increasing operational efficiency. In addition, the low-loss header helps eliminate air and debris [D] from the heating system.
Page 36
Accessories Vitodens 200-W, B2HA 19 to 80 Technical Data Accessories for Vitodens 200-W Low-Loss Header (continued) IMPORTANT Use only a Viessmann supplied temperature sensor. Low-loss header design (Type 80/50 or 120/80) Do not use any other manufacturer’s temperature sensor. Legend...
Standard Equipment Vitodens 200-W, B2HA 19 to 80 Technical Data Standard Equipment The Vitodens 200-W gas-fired condensing boiler with Inox-Radial heat exchanger, modulating MatriX cylinder burner for liquid propane gas and natural gas (available on all models), comes standard with: pressure gage ■...
10.0 1.37 1.40 1.44 1.48 The Vitodens 200-W, B2HA boilers come equipped with Lambda Pro, the industry’s first intelligent combustion management system. The boiler adjusts automatically to any gas type and quality without the need for a fuel conversion kit.
Installation Vitodens 200-W, B2HA 19 to 80 Technical Data Hydraulic Connection System design Viessmann condensing boilers can generally be installed For apartments with less than 860 ft (80 m living in any pumped hot water heating system (closed system). space or for low energy houses with low heat demand The circulation pump is an integral part of the appliance.
The flow rate of the heating circuit is less than the E Heating circuit pump maximum possible water flow rate of the Vitodens 200-W F DHW circulating pump sA B2HA boiler (see page 10 for maximum water flow rate of G DHW storage tank boiler).
Installation Examples Vitodens 200-W, B2HA 19 to 80 Technical Data System Layout 3 Vitodens 200-W, B2HA with... - DHW storage tank - one heating circuit with mixing valve and system separation Installation of ... Legend Vitodens 200-W B2HA boiler with underfloor heating circuit with 3-way mixing valve ■...
Installation Examples Vitodens 200-W, B2HA 19 to 80 Technical Data System Layout 4 Vitodens 200-W, B2HA with... - DHW storage tank - one direct-connected heating circuit - one heating circuit with a mixing valve Legend Installation of ... Vitodens 200-W B2HA boiler with underfloor heating circuit with 3-way mixing valve ■...
Boiler circuit pump than the maximum possible water flow rate of the Mixing valve temperature sensor ? Vitodens 200-W B2HA boiler (see page 10 for maximum Kit for heating circuit with mixing valve water flow rate of boiler). Domestic hot water storage tank The use of a low-loss header is strongly recommended.
28/20 than the maximum possible water flow rate of the Mixing valve temperature sensor ? Vitodens 200-W B2HA boiler (see page 10 for maximum Accessory kit for heating circuit with mixing valve water flow rate of boiler). Heating circuit pumps The use of a low-loss header is strongly recommended.
Installation Examples Vitodens 200-W, B2HA 19 to 80 Technical Data System Layout 7 Vitodens 200-W, B2HA with... - direct-connected heating circuit - one heating circuit with system separation Installation of different heating circuits... radiator heating circuit (high-temp. circuit) Legend ■...
- low-loss header - multiple heating circuits with mixing valves - one heating circuit without mixing valve When designing a system as illustrated above, please contact your local Viessmann Sales Representative for assistance. Legend Vitodens 200-W B2HA boiler with Vitotronic *1 Contact your local Sales Representative for details.
Installation Examples Vitodens 200-W, B2HA 19 to 80 Technical Data System Layout 9 Multiple (up to eight) Vitodens 200-W, models B2HA 45 to 80 with... - multiple heating circuits with mixing valves - low-loss header When designing a multiple Vitodens system as shown...
Installation Examples Vitodens 200-W, B2HA 19 to 80 Technical Data Alternative DHW Connection The following piping diagram reflects an alternative connection for the DHW tank only and applies to system layouts 2, 5, 6 and 8. The boiler control pump logic function must be programmed in the Service Instructions.
Wiring Diagram Vitodens 200-W, B2HA 19 to 80 Technical Data Overview of Electrical Connections, Models B2HA 19, 28, and 35 If any of the original wires as supplied with the appliance must be replaced, it must be replaced with the exact equivalent.
Page 51
Wiring Diagram Vitodens 200-W, B2HA 19 to 80 Technical Data Overview of Electrical Connections, Models B2HA 19, 28 and 35 (continued) Legend Outdoor Temperature Sensor Flow Temperature Sensor/Low Loss Header Boiler Temperature Sensor DHW Temperature Sensor Ionization Electrode Flue Gas temperature Sensor...
Page 52
Wiring Diagram Vitodens 200-W, B2HA 19 to 80 Technical Data Overview of Electrical Connections, Models B2HA 45, 60 and 80 If any of the original wires as supplied with the appliance must be replaced, it must be replaced with the exact equivalent.
Page 53
Wiring Diagram Vitodens 200-W, B2HA 19 to 80 Technical Data Overview of Electrical Connections, Models B2HA 45, 60 and 80 (continued) Legend Outdoor Temperature Sensor Flow Temperature Sensor/Low Loss Header Boiler Temperature Sensor/High Limit Sensor Boiler Temperature Sensor/High Limit Sensor...
(sealed Water connections combustion) regardless of size and ventilation method Vitodens 200-W boilers can be used in any fully pumped of the room in which it is located. hot water heating system. The Vitodens 200-W can be installed, for example, in Minimum system pressure is 0.8 bar (12 psig).
Page 55
System Design Vitodens 200-W, B2HA 19 to 80 Technical Data System Design Considerations (continued) System layout Oxygen diffusion barrier underfloor tubing The max. boiler water temperature for space heating The boiler warranty does not cover leaks resulting from ■ and DHW production is 165° F (74° C) for models corrosion caused by the use of underfloor plastic tubing B2HA 19 to 60 or 176°...
Page 56
Vitodens 200-W, B2HA 19 to 80 Technical Data...