Viessmann VITOCAL 200-G Installation And Service Instructions Manual page 47

Type bwc & bwc-m 201.a06 to a17, 6 to 17 kw single stage heat pump with electric drive, 400 v~ & type bwc-m 201.a06 to a10, 6 to 10 kw single stage heat pump with electric drive, 230 v~
Table of Contents

Advertisement

Electrical connections
Extension PCB on main PCB
Information regarding the connection
values
■ The output given is the recommended
connected load.
■ The total output of all components con-
nected directly to the heat pump con-
trol unit (e.g. pumps, valves, message
facilities, contactors) must not exceed
1000 W.
If the total output is < 1000 W, the indi-
vidual output of a component (e.g.
pump, valve, messaging facility, con-
tactor) may be selected larger than
specified. However, the breaking
capacity of the corresponding relay
must not be exceeded.
■ The stated current indicates the max.
switching current of the switching con-
tact (observe the total current of 5 A).
■ Controls for external heat source and
central fault message are unsuitable
for safety LV.
Plug sXS
Terminals
Function
222.1
Mixer motor control for ex-
ternal heat source
Signal mixer CLOSED
222.2
Mixer motor control for ex-
ternal heat source
Signal mixer OPEN
(cont.)
Set the required parameters during com-
missioning; see from page 66.
Explanation
Connection values:
■ Output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 0.2(0.1) A
Connection values:
■ Output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 0.2(0.1) A
Installation sequence
47