Specification
(cont.)
Type BWC 201.A
Dimensions
Total length
Total width
Total height (programming
unit open)
Weight
Connections
Primary circuit flow/return
Secondary circuit flow/re-
turn
Sound power level (tested
with reference to EN 12102/
EN ISO 9614-2) Weighted
total sound power level at
B0
±3 K
/W35
±5 K
■ At rated heating output
230 V appliances
Type BWC-M 201.A
Output data to EN 14511
(B0/W35, 5 K spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of performance ε
(COP)
Output data to EN 14511
(B0/W35, 10 K spread)
Rated heating output
Cooling capacity
Power consumption
Coefficient of performance ε
(COP)
Brine (primary circuit)
Capacity
Min. flow rate (spread 5 K)
Residual head (at min. flow
rate)
Max. flow temperature
Min. flow temperature
06
mm
844
mm
600
mm
1155
1155
kg
113
G
1½
G
1½
dB(A)
43
06
kW
5.61
kW
4.35
kW
1.36
4.13
kW
5.75
kW
4.53
kW
1.32
4.37
l
1.1
l/h
820
mbar
640
kPa
64
°C
25
°C
–5
Specification
08
10
13
844
844
844
600
600
600
1155
1155
117
129
135
1½
1½
1½
1½
1½
1½
44
44
44
08
7.54
5.94
1.72
4.39
7.57
6.01
1.68
4.50
1.4
1100
640
64
25
–5
17
844
600
1155
148
1½
1½
45
10
9.70
7.61
2.25
4.31
9.97
7.97
2.14
4.65
1.9
1420
640
64
25
–5
103