Troubleshooting by Remote Controller
4.6
Drain Water Level System Abnormality
A3
Error Code
Applicable
All indoor models
Models
Method of Error
By float switch OFF detection
Detection
Error Decision
The error is generated when the water level reaches its upper limit and when the float switch
Conditions
turns OFF.
Defective drain pump
Supposed
Improper drain piping work
Causes
Drain piping clogging
Defective float switch
Defective indoor unit PCB
Defective short circuit connector X15A on PCB
93
SiME281501E
Service Diagnosis