Initial Setting - YASKAWA VS-606V7 Series Instruction Manual

Compact general-purpose inverter (voltage vector control)
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

Initial setting

No.
Terminal
n050
n051
n052
n053
n054
n055
n056
Terminal function at 3-wire sequence selection
When 0 is set at the terminal S3 (n052), terminal S1 becomes run command,
terminal S2 becomes stop command, and terminal S3 becomes FWD/REV
run command.
STOP SW
(NC CONTACT)
• LOCAL/REMOTE selection (setting: 17)
Select operation reference either by the digital operator or by the settings of
run command selection (n003) and frequency reference selection (n004).
LOCAL/REMOTE select is available only during stop.
Open : Run according to the setting of run command selection (n003) or
frequency reference selection (n004).
Closed : Run by frequency reference and run command from the digital
operator.
Initial Setting
S1
1
S2
2
S3
3
S4
5
S5
6
S6
7
S7
10
RUN SW
(NO CONTACT)
S1
Run command
(Run when "closed")
S2
Stop command
(Stop when "open")
S3
FWD/REV run selection
SC
Forward run command (2-wire sequence)
Reverse run command (3-wire sequence)
External fault
Fault reset
Multi-step speed reference 1
Multi-step speed reference 2
JOG command
VS-606V7
(
)
FWD run when "open"
REV run when "closed"
Function
73