Selecting Run/Stop Commands

Switching LOCAL / REMOTE Modes (page 48) to select
Refer to
either the LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run
commands) can be selected by the following method.
LOCAL mode
When Lo (local mode) is selected for digital operator
or when LOCAL / REMOTE switching function is set and the input
terminals are turned ON, run operation is enabled by the
the digital operator, and FWD/REV run is enabled by
(using
or
REMOTE mode
• Select remote mode.
There are following two methods to select remote mode.
1. Select rE (remote mode) for
2. When the local / remote switching function is selected for multi-
function input selection, turn OFF the input terminal to select remote
mode.
• Select operation method by setting the constant n003.
n003=0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications (refer to page 89)
=3: Enables communication card (optional)
• Example for using the multi-function input terminal as operation
reference (two-wire sequence)
FWD RUN/STOP
REV RUN/STOP
For example of three-wire sequence, refer to page 73.
Note: When inverter is operated without the digital operator, always set
the constant n010 to 0.
key).
LO / RE
S1
S2
SC
LO / RE
selection.
IM
n003 : 1 (Initial setting : 0)
n050 : 1 (Initial setting)
n051 : 2 (Initial setting)
ON mode,
or
of
STP
RUN
ON mode
F / R
49