YASKAWA VS-606V7 Series Instruction Manual page 85

Compact general-purpose inverter (voltage vector control)
Hide thumbs Also See for VS-606V7 Series:
Table of Contents

Advertisement

n115 Setting
Setting
The stall prevention level becomes the level set for the constant n094 in
0
all frequency areas.
The following shows that the stall prevention level is automatically
decreased in the constant output range (Max. frequency>Max.
voltage output frequency).
The lower limit is 40% of the set value of n094.
Operation level
1
40% of n094
Accel/decel time selection during stall prevention (n116)
With this function, acceleration/deceleration time when moving to
prevent stalling during operations can be assigned to the two constants,
n021 and n022.
Contest
Name
No.
Accel/decel time
n116
selection during stall
prevention
n116 Setting
Setting
0
Accel / decel time is set by accel / decel time 1 or 2.
1
Accel/decel time is fixed at accel/decel time 2(n021, n022)
• Stall prevention during deceleration (n092)
To prevent overvoltage during deceleration, the inverter automatically
extends the deceleration time according to the value of main circuit DC
voltage. When using an optional braking resistor, set n092 to 1.
Stall prevention during
Setting
deceleration
0
Provided
Not Provided (when braking
1
resistor mounted)
n094
n013
Unit
-
Function
Constant output area
Operation level =
max. voltage output frequency n013
n094 x
output frequency
Lower limit
Output frequency
Setting
Range
0 = Disabled
1 = Enabled
Function
Controls the deceleration
time to prevent overvoltage
fault.
SET
DECEL
TIME
Initial
Setting
0
TIME
85