Technical Specifications - Riello Dialog Plus DLP series User Manual

700-3000 va
Table of Contents

Advertisement

1 -
T
S
ECHNICAL
PECIFICATIONS
MODELS
INPUT
Nominal voltage (±1.5%)
Transfer Voltage Range
- low line transfer
-Low line comeback
-High line transfer
-High line comeback
Nominal frequency
Nominal current
Power factor
Input protection
BYPASS
Accepted voltage range for switch over
Accepted frequency range for switch over
Time taken for switch over
BATTERY
N° batteries / V / Ah
Recharge time
OUTPUT
Nominal voltage
Static variation (4)
Dynamic variation (5)
Wave form
Voltage distortion @ linear load
Voltage distortion @ distorting load (3)
Frequency (6)
Synchronisation range
Current crest factor
Nominal power (3)
Nominal power
OTHER VALUES
Current leakage to ground
AC/AC efficiency
Ambient temperature (7)
Humidity
Protections
Safety certifications
EMC Compliance
Noise
Dimensions H x W x D
Weight
0MNUOC1RUA_GB (614-06498-00)
Dialog Plus 70
[Vac]
[load %]
[Vac]
[Vac]
[Vac]
[Vac]
[Hz]
[A]
3.8
[Va
c]
[msec]
Typically: 2 - Maximum: 4
2 / 12 / 7.2
[h]
4 h to 80% of full charge
[Vac]
[VA]
700
[W]
490
[mA]
86%
[°C]
Excessive battery discharge - overcurrent – short circuit –
overvoltage - undervoltage - thermal
EN62040-1-1 and EEC 73 / 23, 93/68 specifications
EN 50091 - 2 cl. B and EEC 89/336, 92/31, 93/68 specifications
[mm]
[Kg]
12
Dialog Plus 100
Dialog Plus 100 ER
220 / 230 / 240
Based on load percentage
100-80% =160 ± 5
80-70% = 140 ± 5
70-60%= 120 ± 5
60-0%= 110 ± 5
170 ± 5
300 ± 5
285 ± 5
50 / 60
5
≥ 0.97
7A thermal breaker
180 - 264
Selected frequency ±5 %
3 / 12 / 7.2
220 / 230 / 240
1.5%
≤ 5% in 20 msec
Sinusoidal
≤ 3%
≤ 6%
50 – 60 Hz ± 0.2Hz
46-54Hz / 56-64Hz
3 : 1
1000
700
≤ 1.2
88%
0 – 40
< 90% non condensing
< 45 dB(A) at 1 Mt.
231 x 158x 400
14
6.2
--
--
8