Riello Dialog Plus DLP series User Manual page 26

700-3000 va
Table of Contents

Advertisement

T
S
ECHNICAL
PECIFICATIONS
MODELS
INPUT
Nominal voltage (±1.5%)
Transfer Voltage Range
-Low line transfer
-Low line comeback
-High line transfer
-High line comeback
Nominal frequency
Nominal current
Power factor
Input protection
BYPASS
Accepted voltage range for switch over
Accepted frequency range for switch over
Time taken for switch over
BATTERY
N° batteries / V / Ah
Recharge time
OUTPUT
Nominal voltage
Static variation (4)
Dynamic variation (5)
Wave form
Voltage distortion at linear load
Voltage distortion at distorting load (3)
Frequency (6)
Synchronisation range
Current crest factor
Nominal power (3)
Nominal power
OTHER VALUES
Current leakage to ground
AC/AC efficiency
Ambient temperature (7)
Humidity
Protection
Safety certifications
EMC compliance
Hold-up time
Noise
Dimensions H x W x D
Weight
0MNUOC1RUA_GB (614-06498-00)
Dialog Plus 300
[Vac]
[load %]
[Vac]
[Vac]
[Vac]
[Vac]
[Hz]
[A]
14.4
[Vac]
[msec]
Typically: 2 - Maximum: 4
8 / 12 / 7.2
[h]
4 h to 80% of full charge
[Vac]
[VA]
[W]
[mA]
[°C]
Excessive discharge of batteries – overcurrent – short circuit –
overvoltage – undervoltage – thermal
EN 62040-1-1 and EEC 73 / 23, 93/68 specifications
EN 50091 - 2 cl. B and EEC 89/336, 92/31, 93/68 specifications
[msec]
[mm]
[Kg]
35
Dialog Plus 300 ER
220 / 230 / 240
Based on load percentage
100-80% =160 ± 5
80-70% = 140 ± 5
70-60%= 120 ± 5
60-0%= 110 ± 5
170 ± 5
300 ± 5
285 ± 5
50 / 60
16
≥ 0.97
16A thermal Breaker
180 - 264
Selected frequency ±5 %
220 / 230 / 240
1.5%
≤ 5% in 20 ms
Sinusoidal
≤ 3%
≤ 6%
50 ± 0.2Hz autosense
46-54Hz
3 : 1
3000
2100
≤ 1.2
88%
0 – 40
< 90% non condensing
≥ 40
< 45 dB(A) at 1 Mt.
340 x 192 x 460
14
--
--

Hide quick links: