Riello Dialog Plus DLP series User Manual page 25

700-3000 va
Table of Contents

Advertisement

MODELS
INPUT
Nominal Voltage (±1.5%)
Transfer Voltage Range
-Low line transfer
-Low line comeback
-High line transfer
-High line comeback
Nominal frequency
Nominal current
Power factor
Input protection
BYPASS
Accepted voltage range for switch over
Accepted frequency range for switch over
Time taken for switch over
BATTERY
N° batteries / V / Ah
Recharge time
OUTPUT
Nominal voltage
Static variation (4)
Dynamic variation (5)
Wave form
Voltage distortion @ linear load
Voltage distortion @ distorting load (3)
Frequency (6)
Synchronisation range
Current crest factor
Nominal power (3)
Nominal power
OTHER VALUES
Current leakage to ground
AC/AC efficiency
Ambient temperature (7)
Humidity
Protections
Safety certifications
EMC compliance
Noise
Dimensions H x W x D
Weight
T
ECHNICAL SPECIFICATIONS
Dialog Plus 150
[Vac]
[load %]
[Vac]
[Vac]
[Vac]
[Vac]
[Hz]
[A]
7.2
10A thermal breaker 12A thermal breaker
[Vac]
[msec]
4 / 12 / 7.2
[h]
4 h to 80% of full charge
[Vac]
[VA]
1500
[W]
1050
[mA]
[°C]
Excessive battery discharge - overcurrent – short circuit –
overvoltage - undervoltage - thermal
EN62040-1-1 and EEC 73 / 23, 93/68 specifications
EN 50091 - 2 cl. B and EEC 89/336, 92/31, 93/68 specifications
[mm]
231 x 158x 500
[Kg]
19
Dialog Plus 200
Dialog Plus 200 ER
220 / 230 / 240
Based on load percentage
100-80% =160 ± 5
80-70% = 140 ± 5
70-60%= 120 ± 5
60-0%= 110 ± 5
170 ± 5
300 ± 5
285 ± 5
50 / 60
10
≥ 0.97
16A thermal breaker
180 – 264
Selected frequency ±5 %
Typically: 2 - Maximum: 4
8 / 12 / 7.2
220 / 230 / 240
1.5%
≤ 5% in 20 msec
Sinusoidal
≤ 3%
≤ 6%
50 ± 0.2Hz autosense
46-54Hz
3 : 1
2000
1400
≤ 1.2
88%
0 – 40
< 90% non condensing
< 45 dB(A) at 1 Mt.
340 x 192 x 460
34
13.4
--
--
14
25

Hide quick links: