Louver Control; Louver Position; Air Direction Adjustment; Swing - Toshiba Carrier RAS-12EKCV-UL Service Manual

Split type
Table of Contents

Advertisement

Item

7. Louver control

This function controls the air direction of the indoor unit.
1) Louver
• The position is automatically controlled initial setting of "Cooling
position
storage position" Louver : (Directs downward
• The set louver position is stored in memory by the microcomputer,
and the louver returns to the stored position when the next operation
is performed. (Cooling memory position)
The angle of the louver is indicated as the louver closes fully is 0°.
1) Louver position in cooling operation

2) Air direction adjustment

Horizontal
blowing
• Swing operation is performed in width 35° with the stop position as

3) Swing

the center.
• If the stop position exceeds either upper or lower limit position,
swing operation is performed in width 35° from the limit which the
stop position exceeded.
Operation flow and applicable data, etc.
Initial setting of "Cooling storage position"
Louver : (Directs downward 35.3°)
Air direction
Inclined
Blowing
blowing
downward
Upper Limit
Position.
o
17.5
Swing
o
17.5
o
range 35
Fixed Position
Lower Limit
before start
Position.
swing.
).
35.3°
Inclined
Horizontal
blowing
blowing
Upper Limit
o
5
Position.
Fixed
o
30
Position
before start
swing
Swing
Lower Limit
o
range 35
Position
– 34 –
FILE NO. SVM-13071
Description
• The louver position can
be arbitrarily set up by
pressing [FIX] button.
• Swing
When pressing
[SWING] button during
operation, the louver
starts swinging.