10-4-5. Indoor Unit Fixing

1. Pass the pipe through the hole in the wall and
hook the indoor unit on the upper hook of the
installation plate.
2. Swing the indoor unit to right and left to confirm
that it is firmly hooked up on the mounting plate.
3. While pressing the indoor unit onto the wall,
hook in at the lower section of the mounting plate.
Pull the indoor unit toward you to confirm that it is
firmly hooked up on the mounting plate.
Hook here
1
1 Installation
plate
2
Hook
Fig. 10-4-22
• To detach the indoor unit from the mounting plate,
pull the indoor unit toward you while pushing its
bottom up as shown in the figure.
Push
Fig. 10-4-23
10-4-6. Drainage
1. Run the drain hose slopping downward.
NOTE :
• The hole should be made at a slight downward
slant on the outdoor side.
The drain is internally trapped
An external trap is not required
Do not rise the drain hose.
2 in.
(50 mm)
or more
Do not put the
drain hose end
into water.
Fig. 10-4-24
Press (unhook)
Push
Do not form the drain hose
into the waved shape.
Do not put the drain
hose end in the
drainage ditch.
2. Put water in the drain pan and make sure that the
water is drained out.
3. When connecting an extension drain hose,
insulate it with shield pipe.
Drain hose
Arrange the drain pipe for proper drainage from
the unit.
Improper drainage can result in dew-dropping.
This air conditioner has the structure designed
to drain water collected from dew, which forms
on the back of the indoor unit, to the drain pan.
Therefore, do not store the power cord and other
parts at a height above the drain guide.
– 60 –