10-6. SYSTEM REQUIREMENTS

10-6-1. Piping (Field supplied)
Minimum refrigerant line length between the outdoor
unit and indoor unit is
6.6ft. (2m).
Maximum pipe lengths
Allowable Pipe length T
(ft (m))
66 (20)
Fig. 10-6-1
Refrigerant pipe sizes
Liquid side
Outer
Thickness
Diameter
In. (mm)
In. (mm)
Ø1/4 (6.35)
0.03 (0.8)
Insulation
Both lines need to be insulated. Use a minimum
5/16 in (8mm) wall thickness.
Height difference
(Indoor − Outdoor H)
(ft (m))
33 (10)
T
H
Gas side
Thickness
Outer diameter
In. (mm)
In. (mm)
Ø3/8 (9.52)
0.03 (0.8)
Refrigerant charge
Refrigerant charge
Length of refrigerant Pipe
connected to Indoor/
outdoor unit
6.6-50
(2-15m)
50-66
(15-20m)
* Caution during addition of refrigerant Max. amount of
additional refrigerant is 0.22 lbs (100g).
Charge the refrigerant accurately. Overcharging may
cause serious trouble to the compressor.
* Minimum refrigerant pipe is 6.6ft (2m).
Using pipe shorter than that may cause a malfunction of
the compressor or other components.
10-6-2. Power supply Connection and Connecting
Cable
The power supply shall be connected to the outdoor unit
by 3 wires.
The connecting cable between the indoor unit and outdoor
unit is 4 wires.
This cable provides the power for the indoor unit and the
communication signal between the outdoor unit and indoor
unit.
Consult local building codes, NEC (National Electrical Code)
or CEC (Canadian Electrical Code) for special requirements.
The following are the electrical requirements.
Product
Model
Item
MCA
MOCP (MAX Fuse/CB)
Breaker
Connect to
FCU/CDU
Power supply cord
No. of Core
(Not provide)
Size
Interconnecting
No. of Core
cable between
FCU & CDU
Size
(Not provide)
MCA = Minimum Circuit Amps
MOCP = Maximum Over Protection Device Amps
– 63 –
FILE NO. SVM-13071
Unit : ft (m)
Additional refrigerant
None
Add 0.22oz/ft (20g/m) of
Refrigerant for piping that exceeds
50ft (15m) up to 66ft (20m)
FCU
RAS-09EKCV-UL
RAS-12EKCV-UL
CDU
RAS-09EACV-UL
RAS-12EACV-UL
10
15
15A
CDU
3 (L1, L2,
AWG14
4 (L1, L2, S, )
AWG14
13
20
)

Hide quick links: