7-2. Operation Data

<Cooling>
Tempeature
Model name
condition(°C)
Indoor
Outdoor
80/67
98/75
(26.7/19.4) (35/23.9)
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 16 ft (5m)
Standard
RAS-
pressure
P Psia (MPa)
137 to 160
09EKCV-UL
(0.9 to 1.1)
116 to 145
12EKCV-UL
(0.8 to 1.0)
Heat exchanger
pipe temp.
T1 °F (°C)
T2 °F (°C)
54 to 57
99 to 102
(12 to 14)
(37 to 39)
52 to 55
104 to 107
(11 to 13)
(42 to 44)
– 23 –
FILE NO. SVM-13071
Indoor
Outdoor
fan mode
fan mode
High
High
High
High
Compressor
revolution
(rps)
60
77