4.2.66 Logical output signal operation function (LOG1 to LOG6)

The logical output signal operation function allows you to make
the inverter internally perform a logical operation of output
signals.
This function applies to all output signals, except to logical
operation results (LOG1 to LOG6).
Three types of operators (AND, OR, and XOR) are selectable.
Output signal 1
Output signal 2
LOGx (AND)
LOGx (OR)
LOGx (XOR)
The necessary parameters depend on the logical output signal to be operated. The following table lists the
parameters to be set for each logical output signal:
Selected signal
33: Logical output signal 1 (LOG1)
34: Logical output signal 2 (LOG2)
35: Logical output signal 3 (LOG3)
36: Logical output signal 4 (LOG4)
37: Logical output signal 5 (LOG5)
38: Logical output signal 6 (LOG6)
(Example) To output the AND of the running signal (00: RUN) and set the frequency overreached signal
(02: FA2) as the logical output signal 1 (LOG1) to the intelligent output terminal [2]:
- Intelligent output terminal [2] (C002): 33 (LOG1)
- Logical output signal 1 selection 1 (C142): 00 (RUN)
- Logical output signal 1 selection 2 (C143): 02 (FA2)
- Logical output signal 1 operator (C143): 00 (AND)
Item
Terminal function
Alarm relay
terminal function
Logical output
C142/C145/C148/
signal selection 1
C151/C154/C157
Logical output
C143/C146/C149/
signal selection 2
C152/C155/C158
Logical output
C144/C147/C150/
signal operator
C153/C156/C159
selection
Function code
C021 to C025
C026
Selection of "00" to "56" from the
data (except LOG1 to LOG6) output
to intelligent output terminals
Selection of "00" to "56" from the
data (except LOG1 to LOG6) output
to intelligent output terminals
Chapter 4 Explanation of Functions
C021 to C025: Terminal [11] to [15] functions
C026: Alarm relay terminal function
C142: Logical output signal 1 selection 1
C143: Logical output signal 1 selection 2
C144: Logical output signal 1 operator selection
C145: Logical output signal 2 selection 1
C146: Logical output signal 2 selection 2
C147: Logical output signal 2 operator selection
C148: Logical output signal 3 selection 1
C149: Logical output signal 3 selection 2
C150: Logical output signal 3 operator selection
C151: Logical output signal 4 selection 1
C152: Logical output signal 4 selection 2
C153: Logical output signal 4 operator selection
C154: Logical output signal 5 selection 1
C155: Logical output signal 5 selection 2
C156: Logical output signal 5 operator selection
C157: Logical output signal 6 selection 1
C158: Logical output signal 6 selection 2
C159: Logical output signal 6 operator selection
Operation-target 1
Operation-target 2
selection
C142
C145
C148
C151
C154
C157
Data or range of data
33
34
35
36
37
38
00
01
02
4 - 69
Related code
Operator
selection
selection
C143
C144
C146
C147
C149
C150
C152
C153
C155
C156
C158
C159
Description
LOG1: Logical operation result 1
(C142, C143, and C144)
LOG2: Logical operation result 2
(C145, C146, and C147)
LOG3: Logical operation result 3
(C148, C149, and C150)
LOG4: Logical operation result 4
(C151, C152, and C153)
LOG5: Logical operation result 5
(C154, C155, and C156)
LOG6: Logical operation result 6
(C157, C158, and C159)
Selection of operation-target 1
Selection of operation-target 2
AND
OR
XOR