UNDERWRITERS LABORATORIES INFORMATION

The NetworX NX-4V2 holds the following listings from Underwriters Laboratories (US and Canadian):
UL294
UL365
UL609
CAN/ULC-S303-M91
UL985
CAN/ULC-S545-M89
UL1023
ORD-C1023-1974
UL1610
CAN/ULC-S304-M88
UL1635
UL1637
WHEN INSTALLING AN NX-4V2 IN COMPLIANCE WITH UNDERWRITERS LABORATORIES, THE FOLLOWING INSTRUCTIONS
MUST BE OBSERVED:
Initiating and indicating devices must be rated at 11.5 to 12.4 V DC residential, 12.0 V DC commercial.
Force Arming and Auto Arming shall not be enabled.
For residential fire applications, the indicating devices shall be a Wheelock 34T-12 or equivalent.
The "Listen-In" feature shall not be enabled.
The Siren/Bell Test shall be enabled. The auxiliary outputs controlling the audible device require a minimum cutoff time of 15
minutes for commercial burglary, 4 minutes for residential applications, or 30 minutes for Commercial Burglary for Canada.
For residential fire installations, the Dynamic Battery Test time cannot exceed four (4) hours.
Ringback shall be enabled on UL commercial burglary installations.
On commercial burglary installations, the fire initiating circuits shall not be connected.
The Entry-Guard feature shall be disabled.
Group Bypassing shall be disabled.
Delay before dial seizure shall be set to "0".
Total current draw from aux power connections at terminal positions POS, AUX PWR, and SMOKE PWR must not exceed 400 mA.
Remote Downloading shall not be used on UL listed systems.
For residential burglary applications, the maximum entry and exit delay times shall be 45 and 60 seconds respectively. The exit
delay time shall not exceed 60 seconds for commercial burglar alarm applications.
The keyswitch option shall not be used.
The telephone line monitor shall be enabled.
The Telephone Line Cut delay shall not exceed 90 seconds.
24-hour communicator test transmission is required.
For 24 hours of standby power using a 7.0 AH battery, limit auxiliary power load to 140 mA.
For 24 hours of standby power using a 17.2 AH battery, limit auxiliary power load to 400 mA.
The silent keypad option shall not be enabled.
UL has only verified compatibility with the following listed DACRs and formats: Sure-Gard SG-MLR2-DG: 2,9,10,12,13,14; Silent
Knight 9000 - 2,12; FBI - CP220FBI, 13; and Ademco 685: 2,11,12, and 13.
For burglary installations, cross-zoned detectors shall overlap 100 percent in the area of coverage and similar coverage areas
must be used. For example, interior protection is cross-zoned with interior protection, and so on.
Expander trouble must activate the siren (Loc. 37, Segment 2, LED 2)
For UL 1637, expander trouble must activate keypad sounder (Loc. 39, Segment 1, LED 8)
If the Late to Close/Early to Open feature is enabled, the Opening and Closing reports shall be enabled (Loc. 23, Seg. 4, Option 1
and Loc. 23, Seg. 3, Option 1).
For Canadian installations, the class II transformer secure tab shall not be employed.
The 4-wire smoke detector employed shall be rated to operate over the voltage range of 11.5 to 12.4V.
Compatible listed devices: (Special Applications)
o
Bell Output (Sirens): Wheelock models: NS-1215W, NS-121575W, NS4-1215W, NS4-121575W, AS-1215W, AS-121575W
o
Horn / Strobe: System Sensor: S1224MC Strobe series; 1224MC Horn/Strobe series; H12/24 Horn series
o
Smoke Output (4 wire detectors):
ESL: 500N series; 449CTE series; 521 series; 541 series
System Sensor models: 2112/24R; 2112/24TR; 2112/24AT; 2112/ATR; 2112/24AITR; 4WTA-B; 4WTR-B; 4WTAR-B;
4WITAR-B.
Detection Systems: F220-B6C; D273 series
Hochiki: SBC-4/12, 4/12W
44
Access Control System Units
Police Station Connected Burglar Alarms
Local Grade A Mercantile, Police Station Connect with Basic Line Security
* requires #NX-003-C enclosure
Household Fire
Household Burglary
Grade B & C Central Station Burglar Alarm Unit
Digital Alarm Communicator System Units
Home Health Care Signaling
WWW.DIYALARMFORUM.COM
NX-4V2 Control