Remote Control - Daikin VRVIII-S Service Manual

Vrv iii-s r-410a heat pump 50z
Hide thumbs Also See for VRVIII-S:
Table of Contents

Advertisement

Outline of Control (Indoor Unit)
6.1.3 When the Float Switch is Tripped During Heating Operation:
Thermostat
(running)
Humidifier
Float switch
Drain pump
During heating operation, if the float switch is not reset even after the 5 minutes operation, 5
seconds stop, 5 minutes operation cycle ends, operation continues until the switch is reset.
6.1.4 When the Float Switch is Tripped and "AF" is Displayed on the

remote control:

Remote control
display
Float switch
Drain pump
*1 = 5 min.
Note:
If the float switch is tripped five times in succession, a drain malfunction is determined to have
occurred. "AF" is then displayed as operation continues.
58
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
1st time
2nd time
ON
OFF
*1
*1
Remote control "A3" flashing malfunction stop
5 sec.
5 min.
5 min.
"AF" display (running)
3rd time
4th time
5th time
*1
*1
*1
SiENBE34-703
Reset
(VL010)
Enters malfunction treatment
if the float switch is not reset
within 5 minutes.
Remote control "A3" flashing
malfunction stop
*1
*1
(VL011)
Function