Daikin VRVIII-S Service Manual page 260

Vrv iii-s r-410a heat pump 50z
Hide thumbs Also See for VRVIII-S:
Table of Contents

Advertisement

SiENBE34-703
Step
! Make sure that there is no
refrigerant gas left within
the refrigerant circuit
system before performing
the operation
Cut off the suction pipe,
7
discharge pipe and
unloader pipe of
compressor with a pipe
cutter (three places).
Removal Procedure
Procedure
Suction
pipe portion
Compressor
Discharge pipe portion
! The cutting part is in the
compressor side relative to
the brazing part.
! Preliminarily cut off with a
gas welder, a part of the
piping from the end side to
the soldered portion, which
have remained after being
cut using a pipe cutter,
before replacing with a new
compressor.
Unloader
piping portion
Refrigerant oil in the compressor
may catch fire, so prepare wet
cloth so as to extinguish a fire
rapidly.
If refrigerant gas leaks during
operation, ventilate the room.
(The exposure of refrigerant gas
to a fire causes generates toxic
gas.)
Do not suffer burns due to
contact with piping etc. heated
by a gas welder.
RXYSQ4 · 5 · 6 P7Y1B
Points
Warning
Warning
Caution