SiENBE34-703
Heating
When heating, the hot air rises to the top of the room, resulting in the temperature being lower
near the floor where the occupants are. When controlling by body thermostat sensor only, the
unit may therefore be turned off by the thermostat before the lower part of the room reaches the
preset temperature. The temperature can be controlled so the lower part of the room where the
occupants are doesn't become cold by widening the range in which thermostat sensor in remote
control can be used so that suction temperature is higher than the preset temperature.
32
30
Preset Temperature
(Ts)
28
26
24
22
20
18
16
15
12
! Ex: When heating
Assuming the preset temperature in the figure above is 24°C, and the suction
temperature has changed from 18°C to 28°C (A → D):
(This example also assumes there are several other air conditioners, the VRV system is off, and
that temperature changes even when the thermostat sensor is off.)
Body thermostat sensor is used for temperatures from 18°C to 25°C (A → C).
remote control thermostat sensor is used for temperatures from 25°C to 28°C (C → D).
And, assuming suction temperature has changed from 28°C to 18°C (D → A):
remote control thermostat sensor is used for temperatures from 28°C to 23°C (D → B).
Body thermostat sensor is used for temperatures from 23°C to 18°C (B → A).
Function
A
TH1 = Ts + 1 ≤ 31°C
14
16
18
20
Range in which thermostat sensor
in remote control can be used
TH1 = Ts – 1
B
C
D
22
24
26
28
Range in which body
thermostat sensor
can be used
Outline of Control (Indoor Unit)
TH1 = Ts + 12 ≤ 33°C
TH1 = Ts + 10 ≤ 31°C
30
32
34
Suction temperature (TH1)
Differential
61