Daikin VRVIII-S Service Manual page 85

Vrv iii-s r-410a heat pump 50z
Hide thumbs Also See for VRVIII-S:
Table of Contents

Advertisement

Field Setting
3.1.4 Setting Contents and Code No. – VRV Indoor Unit
VRV
Mode
Setting
Switch
system
No.
No.
indoor
Note 2
unit
10(20)
0
Filter contamination heavy/
settings
light (Setting for display
time to clean air filter)
(Sets display time to clean
air filter to half when there is
heavy filter contamination.)
1
Long life filter type
2
Thermostat sensor in remote control
3
Display time to clean air filter
calculation (Set when filter sign is not
to be displayed.)
12(22)
0
Optional accessories output selection
(field selection of output for adapter for
wiring)
1
ON/OFF input from outside (Set when
ON/OFF is to be controlled from
outside.)
2
Thermostat differential changeover
(Set when remote sensor is to be
used.)
3
OFF by thermostat fan speed
4
Automatic mode differential (automatic
temperature differential setting for VRV
system heat recovery series cool/heat)
5
Power failure automatic reset
13(23)
0
High air outlet velocity
(Set when installed in place with ceiling
higher than 2.7 m.)
1
Selection of air flow direction
(Set when a blocking pad kit has been
installed.)
3
Air flow direction adjustment (Set at
installation of decoration panel.)
4
Field set air flow position setting
5
Field set fan speed selection
(fan speed control by air discharge
outlet for phase control)
15(25)
1
Thermostat OFF excess humidity
2
Direct duct connection
(when the indoor unit and heat reclaim
ventilation unit are connected by duct
directly.) ∗Note 6
3
Drain pump humidifier interlock
selection
5
Field set selection for individual
ventilation setting by remote control
6
Field set selection for individual
ventilation setting by remote control
Notes :
1. Settings are made simultaneously for the entire group, however, if you select the mode No.
2. The mode numbers inside parentheses cannot be used by infrared remote controls, so they
3. Marked
4. Do not make settings other than those described above. Nothing is displayed for functions
5. "88" may be displayed to indicate the remote control is resetting when returning to the
6. If the setting mode to "Equipped", heat reclaim ventilation fan conducts the fan residual
74
Setting Contents
Super
long life
filter
Long life
filter
Standard
filter
inside parentheses, you can also set by each individual unit. Setting changes however
cannot be checked except in the individual mode for those in parentheses.
cannot be set individually. Setting changes also cannot be checked.
are factory set.
the indoor unit is not equipped with.
normal mode.
operation by linking to indoor unit.
Second Code No.(Note 3)
01
02
Light
Approx.
Heavy
Approx.
10,000
5,000
hrs.
Approx.
Approx.
2,500
1,250
hrs.
Approx.
Approx.
200
hrs.
Long life filter
Ultra long life
filter
Use
No use
Display
No display
Indoor unit
turned ON by
thermostat
Forced OFF
ON/OFF control
1°C
0.5°C
LL
Set fan speed
01:0
02:1
03:2
Not equipped
Equipped
N
H
F (4 directions)
T (3 directions)
Equipped
Not equipped
Draft prevention
Standard
Standard
Optional
accessory 1
Not equipped
Equipped
Not equipped
Equipped
Not equipped
Equipped
Not equipped
Equipped
Not equipped
Equipped
SiENBE34-703
03
hrs.
hrs.
100
hrs.
Operation output
External
protection device
input
04:3
05:4
06:5
07:6
S
W (2 directions)
Ceiling Soiling
prevention
Optional
accessory 2
Test Operation
04
Malfunction
output
08:7

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents