SiENBE34-703
Caution
Capacity Setting after changing the main P.C.Board(A1P) to spare parts P.C.B.
When you change the main P.C.Board(A1P) to spare parts P.C.B., please carry out the following
setting.
Please Attach the Capacity Setting Adapter corresponding to Capacity Class (ex. 112, 140, 160) in connector X51A.
(See Below)
Capacity Setting Adapter
Capacity Class
1
2
3
Position of Attaching the Capacity Setting Adapter
A1P
Test Operation
4 (112)
CAPACITY SETTING ADAPTER (for 100/J112)
5 (140)
CAPACITY SETTING ADAPTER (for 125/J140)
6 (160)
CAPACITY SETTING ADAPTER (for 140/J160)
Note
Field Setting
X51A
Position of Attaching
the Capacity Setting Adapter
X51A
85