RXYSQ4 · 5 · 6 P7Y1B
Step
2
Remove the clamp
material.
3
Remove the four fixing
screws for fan motor
and then remove the
fan motor.
246
Procedure
Fan
motor
Mount the fan motor with its mark ")"
positioned toward the bottom.
Lead wire for
fan motor
Earth wire
Clamp material
D cut
SiENBE34-703
Points
! Pull off the connector while
supporting its body and
pushing the engaging click,
without pulling its lead wires.
! Caution on mounting the
motor
If the motor lead wires are
not fixed by using the clamp
material, it may always
damage the lead wire
because the lead wires
twined around the fan.
Lead wire
Propeller fan
! When mounting the propeller
fan, make the D cut
correspond to the hole of the
fan.