Daikin VRVIII-S Service Manual page 42

Vrv iii-s r-410a heat pump 50z
Hide thumbs Also See for VRVIII-S:
Table of Contents

Advertisement

SiENBE34-703
Ceiling Suspended Cassette Type
Indoor Unit
Model
Connection Unit
H1 Cooling Capacity (19.5°CWB)
H2 Cooling Capacity (19.0°CWB)
H3 Heating Capacity
Casing Color
Dimensions: (H×W×D)
Rows×Stages×Fin Pitch
Coil (Cross
Fin Coil)
Face Area
Model
Type
Motor Output × Number
of Units
Fan
Air Flow Rate (H/L)
Drive
Temperature Control
Sound Absorbing Thermal Insulation Material
Liquid Pipes
Piping
Gas Pipes
Connections
Drain Pipe
Machine Weight (Mass)
H5 Sound Level (H/L)
Safety Devices
Standard Accessories
Drawing No.
Notes:
H1 Indoor temp. : 27°CDB, 19.5°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
H2 Indoor temp. : 27°CDB, 19.0°CWB / outdoor temp.: 35°CDB / Equivalent piping length: 7.5m, level
H3 Indoor temp. : 20°CDB / outdoor temp.: 7°CDB, 6°CWB / Equivalent piping length: 7.5m, level difference:
4 Capacities are net, including a deduction for cooling (an additional for heating) for indoor fan motor heat.
H5 Anechoic chamber conversion value, measured at a point 1.5m downward from the unit center. These
Specifications
FXUQ71MAV1
BEVQ71MAVE
kcal/h
7,100
Btu/h
28,300
kW
8.3
kW
8.0
kcal/h
7,700
Btu/h
30,700
kW
9.0
White (10Y9/0.5)
mm
165×895×895
mm
3×6×1.5
0.265
QTS48A10M
Turbo Fan
W
45×1
m³/min
19/14
cfm
671/494
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
φ9.5 (Flare Connection)
mm
φ15.9 (Flare Connection)
mm
mm
I.Dφ20×O.Dφ26
kg
25
dBA
40/35
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
difference: 0m.
difference: 0m.
0m. (Heat pump only)
values are normally somewhat higher during actual operation as a result of ambient conditions.
FXUQ100MAV1
BEVQ100MAVE
10,000
39,600
11.6
11.2
10,800
42,700
12.5
White (10Y9/0.5)
230×895×895
3×8×1.5
0.353
QTS50B15M
Turbo Fan
90×1
29/21
1,024/741
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
φ9.5 (Flare Connection)
φ15.9 (Flare Connection)
I.Dφ20×O.Dφ26
31
43/38
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
C:4D045395A
Specifications
FXUQ125MAV1
BEVQ125MAVE
12,500
49,500
14.5
14.0
12,000
47,800
14.0
White (10Y9/0.5)
230×895×895
3×8×1.5
0.353
QTS50B15M
Turbo Fan
90×1
32/23
1,130/812
Direct Drive
Microprocessor Thermostat for
Cooling and Heating
Heat Resistant Foamed Polyethylene,
Regular Foamed Polyethylene
φ9.5 (Flare Connection)
φ15.9 (Flare Connection)
I.Dφ20×O.Dφ26
31
44/39
Thermal Protector for Fan Motor
Operation Manual, Installation
Manual, Drain Hose, Clamp Metal,
Insulation for Fitting, Sealing Pads,
Clamps, Screws, Washers, Holding
Plate.
Conversion Formula
kcal/h=kW×860
Btu/h=kW×3412
cfm=m³/min×35.3
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents