Daikin VRVIII-S Service Manual page 128

Vrv iii-s r-410a heat pump 50z
Hide thumbs Also See for VRVIII-S:
Table of Contents

Advertisement

SiENBE34-703
Malfunction
code
Outdoor Unit
LA
LC
P1
System
U0
U1
U2
U3
U4
U5
U5
U7
U8
U9
UA
UC
UE
UF
UH
Central
UE
remote
control and
M1
Schedule
Timer
M8
MA
MC
Heat
64
Reclaim
65
Ventilation
68
6A
6A
6F
94
The system operates for malfunction codes indicated in black squares, however, be sure to check and repair.
Troubleshooting
Operation
Inspection
Unit No.
lamp
display
9
9
9
9
9
9
8
7
9
9
9
9
9
9
9
9
9
9
7
8
9
9
9
9
9
9
9
9
8
8
9
9
9
9
9
9
9
9
8 or 7
9
8 or 7
9
8 or 7
9
8 or 7
9
8
7
8
7
8
7
8
7
9
9
8
7
9
9
Malfunction contents
Malfunction of power unit
9
Malfunction of transmission between inverter and
9
control PC board
High voltage of capacitor in main inverter circuit.
9
Low pressure drop due to refrigerant shortage or
9
electronic expansion valve failure
Reverse phase / open phase
9
Power supply insufficient or instantaneous failure
9
Check operation is not completed.
9
Malfunction of transmission between indoor and
9
outdoor units
Malfunction of transmission between remote control
9
and indoor unit
Failure of remote control PC board or setting during
7
control by remote control
Malfunction of transmission between outdoor units
9
Malfunction of transmission between main and sub
7
remote controls (malfunction of sub remote control)
Malfunction of transmission between indoor unit and
9
outdoor unit in the same system
Improper combination of indoor and outdoor units,
9
indoor units and remote control
Address duplication of central remote control
8
Malfunction of transmission between central remote
9
control and indoor unit
Refrigerant system not set, incompatible wiring /
9
piping
Malfunction of system, refrigerant system address
9
undefined
Malfunction of transmission between central remote
9
control and indoor unit
Central remote control PC board defect
9
Schedule timer PC board defect
Malfunction of transmission between optional
9
controllers for centralized control
Improper combination of optional controllers for
9
centralized control
Address duplication, improper setting
9
Indoor unit's air thermistor error
9
Outside air thermistor error
9
Malfunction of HVU
9
Damper system alarm
9
Damper system + thermistor error
9
Malfunction of simple remote control
9
Internal transmission error
9
Troubleshooting by Remote Control
8: ON
7: OFF
9: Blink
Page
Referred
162
163
164
166
168
169
171
171
172
173
175
176
177
179
180
181
182
183
184
186
117

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents