Assemble Slip Sections; Secure The Vent Sections - Heat & Glo RED60 Installation Manual

Installation and appliance setup
Hide thumbs Also See for RED60:
Table of Contents

Advertisement

B. Assemble Slip Sections
• Slide the inner fl ue of the slip section into the inner fl ue
of the pipe section and the outer fl ue of the slip section
over the outer fl ue of the pipe section. See Figure 7.5.
• Slide together to the desired length.
Figure 7.5 Slip Section Pilot Holes
• Maintain a 1-1/2 in. (38 mm) overlap between the slip
section and the pipe section.
• Secure the pipe and slip section with two screws no
longer than 1/2 in. (13 mm), using the pilot holes in the
slip section. See Figure 7.6.
Figure 7.6 Screws into Slip Section
• Continue adding pipe as necessary following instructions
in "Assembling Pipe Sections."
NOTICE: If slip section is too long, the inner and outer
fl ues of the slip section can be cut to the desired length.
NOTICE: When installing a vent system with an HRC
termination cap, all pipe system joints shall be sealed using
a silicone sealant with a minimum of 300ºF continuous
exposure rating.
• Apply a bead of silicone sealant inside the female outer
pipe joint prior to joining sections.
• Only outer pipes are sealed, sealing the inner fl ue is not
required.
• All unit collar, pipe, slip section, elbow and cap outer
fl ues shall be sealed.
46
Pilot hole
Pilot hole
Heat & Glo • RED60 Installation Manual • 2159-980 Rev. D • 11/13
C. Secure The Vent Sections
• Vertical runs originating off the top of the appliance, with no
offsets, must be supported every every 8 ft. (2.44 m) after the
maximum allowed 25 ft. (7.62 m) of unsupported rise.
• Vertical runs, after any elbow, must be supported
every 5 ft. (1.52 m).
• Horizontal runs must be supported every 5 feet (1.52
m).
• Vent supports or plumbers strap (spaced 120º apart)
may be used to support. See fi gures 7.7 and 7.8.
• Wall shield fi restops may be used to provide horizontal
support.
• Ceiling fi restops have tabs that may be used to provide
vertical support.
WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate.
Use vent run supports and connect vent sections per in-
stallation instructions. DO NOT allow vent to sag below
connection point to appliance.
Figure 7.7 Securing Vertical Pipe Sections
Figure 7.8 Securing Horizontal Pipe Sections
120º
120º

Advertisement

Table of Contents
loading

Table of Contents