Mitsubishi Heavy Industries FDTC40ZHXV Technical Manual page 325

Packaged air-conditioner split system, air to air heat pump type
Hide thumbs Also See for FDTC40ZHXV:
Table of Contents

Advertisement

E39
Note (1) ( ) is for model 40~60.
1. Applicable model
All models
2. Error detection method
Detection of anomalously low
temperature (resistance) on
the discharge pipe temperature
thermistor
3. Condition of Error displayed
When the temperature thermistor
detects -10°C or lower for 5
seconds continuously within
10 minutes to 10 minutes 20
seconds after the compressor
ON, the compressor stops. After
3-minutes delay, the compressor
starts again automatically, but
if this anomalous temperature
is detected 3 times within 40
minutes.
4. Presumable cause
• Defective outdoor control
PCB
• Broken thermistor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
Keeps flashing Stays Off
Keeps flashing 1(8) time flash
5. Troubleshooting
Diagnosis
304
Discharge pipe
temperature thermistor anomaly
Countermeasure
Correct connector.
Defective discharge pipe
temperature thermistor
Replace.
Defective outdoor control
PCB Replace.
(Defective temperature
thermistor input circuit)