Advertisement

E8
1. Applicable model
All models
2. Error detection method
Indoor heat exchanger
temperature thermistor (ThI-R1,
R2, R3)
3. Condition of Error displayed
When it is detected 5 times
within 60 minutes from initial
detection or when the overload
condition is detected for 6
minutes continuously.
4. Presumable cause
• Clogged air filter
• Defective indoor heat
exchanger temperature
thermistor connector
• Defective indoor heat
exchanger temperature
thermistor
• Anomalous refrigerant system
Note:
During heating operation; After starting compressor, compressor rotation speed is decreased by detecting indoor heat
exchanger temperature (Thi-R) in order to control high pressure.
Keeps flashing 1 time flash
Keeps flashing Stays Off
5. Troubleshooting
Diagnosis
289
Heating overload operation
Countermeasure
Wash.
Defective indoor heat
exchanger temperature
thermistor connector
Correct.
Defective indoor heat
exchanger temperature
thermistor.
Check refrigerant system.
Adjust