E6
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected on the indoor heat
exchanger thermistor (ThI-R1,
R2 or R3).
3. Condition of Error displayed
• When the temperature
thermistor detects -50°C
or lower for 5 seconds
continuously, the compressor
stops. After 3-minutes delay,
the compressor starts again
automatically, but if this
error occurs again within
60 minutes after the initial
detection.
• Or if 70°C or higher is
detected for 5 seconds
continuously.
4. Presumable cause
• Defective indoor heat
exchanger thermistor
connector
• Indoor heat exchanger
temperature thermistor
anomaly
• Faulty indoor control PCB
Note:
Keeps flashing 1 time flash
Keeps flashing Stays Off
5. Troubleshooting
Diagnosis
287
–
Indoor heat exchanger
temperature thermistor anomaly
–
Countermeasure
Correct.
Insert connector
securely.
Defective indoor heat
exchanger temperature
thermistor
Replace.
Defective indoor control
PCB
Replace.
(Defective indoor unit heat
exchanger temperature
thermistor input circuit)