• External static pressure table
Duct specs.
Air flow
(m
/min)
Stan-
3
Model
dard
FDUM50V
14
18
35/30
FDUM60V
FDUM71V
20
30/25
28
50/50
FDUM100V
FDUMA125V, 140V
34
50/45
Notes (1) 1 spot closing: Round duct flange at center is removed and shield with a
special panel (option).
(2) Standard: ø200 duct are installed at all blowout holes.
(3) Square duct: All round ducts are removed and replaced with special
square duct flanges (option).
(4) When using the high speed setting, turn the dip switch SW9-4 on the
indoor PCB to the ON position.
(When setting from the remote controller, select "Hi CEILNG 1")
Unit : Pa (50Hz/60Hz)
1 spot
Standard
closing
High
(4)
Stan-
High
(4)
speed
speed
dard
-
-
50/40
85/90
70/85
50/40
85/100
65/80
50/45
85/100
80/90
60/60
90/100
75/90
60/55
85/100
How to interpret the blower characteristics table
Example : Case of FDUM60V (50Hz)
Square duct
40
Stan-
High
(1)
dard
speed
50/45
90/90
20
55/50
90/100
55/50
90/105
65/65
95/105
65/65
95/105
–10
–20
130
-
-
2-spot blower
2-spot blower
internal resistance
internal resistance
0
3-spot blower
3-spot blower
internal resistance
internal resistance
Square duct blower
internal resistance
internal resistance
13
14
16
18
1 2-spot blowout.....................
Internal resistance increases more than
the standard 3-spot blowout.Approx.
14Pa at 17m
/min
3
2 Square duct blowout...........
Internal resistance decreases more than
the standard round duct (ø200 3-spot).
3Pa at 17m
/min. (External static
3
pressure increases in reverse.)
20