E7
1. Applicable model
All models
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor return air
temperature thermistor (Thi-A)
3. Condition of Error displayed
• When the temperature thermistor
detects -50°C or lower for
5 seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
• Or if 48°C or higher is detected
for 5 seconds continuously.
4. Presumable cause
• Defective return air
temperature thermistor
connector
• Defective return air
temperature thermistor
• Faulty indoor control PCB
Note:
Keeps flashing 1 time flash
Keeps flashing Stays Off
5. Troubleshooting
Diagnosis
288
–
Return air temperature
thermistor anomaly
–
Countermeasure
Correct.
Connect
connector.
Defective return air
temperature thermistor
Replace.
Defective indoor control
PCB
Replace.
(Defective return air
temperature thermistor
input circuit)