Model FDT100VNV
Item
Nominal cooling capacity
(1)
Nominal heating capacity
(1)
Power source
Cooling power consumption
Running current (Cooling)
Power factor (Cooling)
Heating power consumption
Running current (Heating)
Power factor (Heating)
Inrush current (L.R.A) <Max. running current>
Noise level
Exterior dimensions
Height × Width × Depth
Net weight
Refrigerant equipment
Compressor type & Q'ty
Starting method
Heat exchanger
Refrigerant control
Refrigerant
Quantity
Refrigerant oil
Defrost control
Air handling equipment
Fan type & Q'ty
Motor
Starting method
Air flow
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Electric heater
Operation control
Operation switch
Room temperature control
Safety equipment
Installation data
Refrigerant piping size
Connecting method
Drain hose
Insulation for piping
Accessories
Optional parts
Notes (1) The data are measured at the following conditions.
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 "UNITARY AIR-CONDITIONERS"
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
Model
kW
kW
kW
A
%
kW
A
%
A
dB(A)
mm
kg
Louver fin & inner grooved tubing
kg
r
W
CMM
Pocket plastic net × 1 (washable)
W
Wired remote control switch (Optional : RC-E3)
Wireless kit (Optional : RCN-T-36W-E)
Overload protection for fan motor.
mm
(in)
Connectable with VP20 (I.D. 20mm, O.D. 26mm)
Indoor air temperature
Item
DB
27˚C
20˚C
FDT100VNV
FDT100V
10.0 [4.0~11.2]
11.2 [4.0~12.5]
1 Phase, 220-240V 50Hz/220V 60Hz
Hi:40 Me:37 Lo:35
Unit 298 × 840 × 840
Panel 35 × 950 × 950
32.5 (Unit:27 Panel:5.5)
Microcomputer controlled de-icer
Turbo fan × 1
140 × 1
Direct line start
Hi:27 Me:24 Lo:20
Possible
Rubber sleeve (for fan motor)
Thermostat by electronics
Frost protection thermostat.
Liquid line: φ9.52 (3/8ʺ) Gas line: φ15.88 (5/8ʺ)
Flare piping
Necessary (both Liquid & Gas lines)
Mounting kit. Drain hose
Decorative Panel
Outdoor air temperature
WB
DB
19˚C
35˚C
7˚C
16
-
-
FDC100VN
2.76/2.76
12.1/12.7
99/99
2.74/2.74
12.0/12.6
99/99
5 <24>
49
845 × 970 × 370
81
RMT5126MDE2 × 1
Direct line start
Straight fin & inner grooved tubing
Electronic expansion valve
R410A
3.8 [Pre-charged up to the piping length of 30m]
0.9 (M-MA68)
Propeller fan × 1
86 × 1
Direct line start
Cooling: 75, Heating: 73
Rubber sleeve (for compressor)
20 (Crank case heater)
– (Indoor unit side)
Internal thermostat for fan motor.
Anomalous discharge temperature protection.
Holes size φ20 × 3 pcs
(T-PSA-36W-E)
WB
24˚C
6˚C
Standards
ISO-T1
* •

Hide quick links: