Mitsubishi Heavy Industries FDTC40ZHXV Technical Manual page 265

Packaged air-conditioner split system, air to air heat pump type
Hide thumbs Also See for FDTC40ZHXV:
Table of Contents

Advertisement

(ii) Outdoor unit side
1)
Model SRC40~60
Indoor unit control
Remote controller
PCB
Error
Red LED Red LED Green LED Red LED
code
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
Keeps
flashing
flashing
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
flashing
Stays OFF
flashing
Note (1) * mark in the Description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by replacing the
part, it is judged consequently that the replaced part was defective.
Outdoor unit
control PCB
Location of
trouble
Keeps
1 time flash Power supply wires • Anomalous current on inverter primary side
Installation,
operation status
Outdoor unit
Keeps
heat exchanger
8 times flash
temperature
thermistor
Outdoor unit
control PCB
Installation,
operation status
Discharge pipe
Keeps
8 times flash
temperature
thermistor
Outdoor unit
control PCB
Outdoor unit
heat exchanger
Keeps
temperature
8 times flash
thermistor
Outdoor unit
control PCB
Ambient air
temperature
Keeps
8 times flash
thermistor
Outdoor unit
control PCB
Discharge pipe
temperature
Keeps
8 times flash
thermistor
Outdoor unit
control PCB
Outdoor unit
control PCB
Keeps
1 time flash
compressor
Installation,
operation status
Outdoor unit
Keeps
1 time flash
control PCB power
transistor
DC fan motor
Keeps
Keeps
Outdoor unit
flashing
control PCB
Operation status
Keeps
2 times flash
Installation status • Service valve closing operation
Compressor
Keeps
2 times flash
outdoor unit control
PCB
Keeps
7 times flash
Compressor
Description of trouble
• Higher outdoor unit heat exchanger temperature
• Defective outdoor unit heat exchanger temperature thermistor
*• Defective outdoor unit control PCB (Defective temperature sensor
input circuit)?
• Higher discharge temperature
• Defective discharge pipe temperature thermistor
*• Defective outdoor unit control PCB (Defective temperature sensor
input circuit)?
• Defective outdoor unit heat exchanger temperature thermistor,
broken wire or poor connector connection
*• Defective outdoor unit control PCB (Defective temperature sensor
input circuit)?
• Defective ambient air temperature thermistor, broken wire or poor
connector connection
*• Defective outdoor unit control PCB (Defective temperature sensor
input circuit)?
• Defective discharge pipe temperature thermistor, broken wire or
poor connector connection
*• Defective outdoor unit control PCB (Defective temperature sensor
input circuit)?
• Current cut (Anomalous compressor over-current)
• Service valve closing operation
• Anomalous inverter over-voltage
• Defective DC fan motor
• Defective outdoor unit control PCB
• Shortage in refrigerant quantity
• Anomalous compressor startup
• Anomalous compressor rotor lock
248
Reference
Repair method
page
Repair
296
Repair
Replacement,
repair of
299
temperature
thermistor
Replacement of
PCB
Repair
Replacement,
repair of
301
temperature
thermistor
Replacement of
PCB
Replacement,
repair of
temperature
302
thermistor
Replacement of
PCB
Replacement,
repair of
temperature
303
thermistor
Replacement of
PCB
Replacement,
repair of
temperature
304
thermistor
Replacement of
PCB
Replacement of
PCB
307, 308
Repair
Repair
310
PCB replacement
Replacement
311
Repair
319
Service valve
opening check
Replacement
320
Replacement
322

Hide quick links: