E5
1. Applicable model
All models
2. Error detection method
When normal communication
between indoor and outdoor
unit is interrupted for more than
2 minutes.
3. Condition of Error displayed
Same as above is detected
during operation.
4. Presumable cause
• Unit No. setting error
• Broken remote controller wire
• Faulty remote controller wire
connection
• Defective indoor control PCB
Note:
Pressing the pump-down switch cancels communications between indoor and outdoor unit so that "communication
error-E5" is displayed on indoor unit and remote controller, but it is normal.
Keeps flashing See below
Keeps flashing 2 times flash
5. Troubleshooting
Diagnosis
286
Communication error during operation
Countermeasure
Repair signal wires.
Repair signal wires.
To the diagnosis of
"
"
Unit is normal.
(Malfunction by temporary
noise, etc.)
Defective outdoor control
PCB (Defective network
communication circuit)
Replace.
Unit is normal.
(Malfunction by temporary
noise, etc.)