Mitsubishi Heavy Industries FDTC40ZHXV Technical Manual page 292

Packaged air-conditioner split system, air to air heat pump type
Hide thumbs Also See for FDTC40ZHXV:
Table of Contents

Advertisement

None
1. Applicable model
All models
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
Note:
5. Troubleshooting
Diagnosis
271
Excessive noise/vibration (2/3)
Countermeasure
Rearrange the piping to
avoid contact with the
casing.
It is noise/vibration that
is generated when the
refrigerant gas or liquid
flow through inside of
piping of air-conditioner.
It is likely to occur
particularly during cooling
or defrosting in the heating
mode. It is normal.
The noise/vibration occurs
when the refrigerant starts
or stops flowing. It is
normal.
When the defrosting starts
or stops during heating,
the refrigerant flow is
reversed due to switching
4-way valve. This causes
a large change in pressure
which produces a blowing
sound. It may accompany
also the hissing sounds as
mentioned above. They are
normal.
After the start or stop of
heating operation or during
defrosting, abrupt changes
in temperature cause resin
parts to shrink or expand.
This is normal.
It is the sound produced
by the drain pump that
discharges drain from the
indoor unit. The pump
continues to run for 5
minutes after stopping the
cooling operation. This is
normal.
Apply the damper sealant
at places considered to
be the sources such as
the pressure reducing
mechanism (expansion
valve), capillary, etc.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents