Mitsubishi Heavy Industries FDTC40ZHXV Technical Manual

Mitsubishi Heavy Industries FDTC40ZHXV Technical Manual

Packaged air-conditioner split system, air to air heat pump type
Hide thumbs Also See for FDTC40ZHXV:

Advertisement

TECHNI CAL M ANUAL
Col l e c t i on da t a
PACKAGED AIR-CONDITIONER
(Split system, Air to air heat pump type)
CEILING CASSETTE-4 WAY COMPACT
FDTC40ZHXV
FDTC71VNPV
50ZHXV
100VNPV
100VSPV
CEILING CASSETTE-4 WAY TYPE
FDT40ZHXV
FDT71VNPV
50ZHXV
100VNPV
60ZHXV
100VSPV
71VNV
125VNPV
100VNV
125VSPV
100VSV
140VNPV
125VNV
140VSPV
200VSPV
125VSV
140VNV
250VSPV
140VSV
MULTI-TYPE (V-MULTI)
PACKAGED AIR-CONDITIONER
(OUTDOOR UNIT)
FDC71VN
100VN
100VS
125VN
125VS
140VN
140VS
200VS
250VS
-TYPE
(600×600mm)
FDTC140VNTV
140VSTV
FDT140VNTV
140VSTV
200VSTV
FDT200VSDV
250VSDV
(INDOOR UNIT)
FDTC40V
FDT40V
50V
50V
60V
71V
100V
125V
Manual No. '08 PAC-T-118
updated July 08, 2011
CEILING SUSPENDED TYPE
FDEN40ZHXV
FDEN71VNPV
50ZHXV
100VNPV
60ZHXV
100VSPV
71VNV
125VNPV
100VNV
125VSPV
100VSV
140VNPV
125VNV
140VSPV
125VSV
200VSPV
140VNV
250VSPV
140VSV
DUCT CONNECTED-MIDDLE STATIC PRESSURE- TYPE
FDUM50ZHXV
FDUM100VNPV
60ZHXV
100VSPV
71VNV
125VNPV
100VNV
125VSPV
100VSV
140VNPV
125VNV
140VSPV
125VSV
200VSPV
140VNV
250VSPV
140VSV
DUCT CONNECTED-HIGH STATIC PRESSURE- TYPE
FDU71VNV
100VNV
100VSV
125VNV
125VSV
140VNV
140VSV
200VSV
250VSV
FDEN40V
FDUM50V
50V
60V
60V
71V
71V
100V
100V
125V
125V
FDEN140VNTV
140VSTV
200VSTV
FDUM140VNTV
140VSTV
200VSTV

Advertisement

Table of Contents
loading

Summary of Contents for Mitsubishi Heavy Industries FDTC40ZHXV

  • Page 1 TECHNI CAL M ANUAL Col l e c t i on da t a PACKAGED AIR-CONDITIONER (Split system, Air to air heat pump type) CEILING CASSETTE-4 WAY COMPACT -TYPE CEILING SUSPENDED TYPE (600×600mm) FDTC40ZHXV FDTC71VNPV FDTC140VNTV FDEN40ZHXV FDEN71VNPV FDEN140VNTV 50ZHXV 100VNPV...
  • Page 4: Table Of Contents

    M M odels SRC40 ~ 60 models ................1 1 62 Models FDC71 ~ 250 models ................1 1 68 1.5 APPLICATION DATA ....................178 1.5.1 Installation of indoor unit ..................1 1 81 (1) Ceiling cassette-4 way compact (600×600mm)-type (FDTC) ......181 (2) Ceiling cassette-4 way-type (FDT) ................
  • Page 5 (1) All models employ R410A, with RoHS compliance. (2) Industry leading COP. Thanks to achievement of the highest COP level in the industry, the energy consumption has been cut by 39~49% compared with our former models (constant speed models). (3) Energy labeling “Class A” MHI models have cleared the class A standard, the highest energy saving level, with their high COP (coefficient of performance).
  • Page 6 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:38 Lo:35 × × × × × × × × –...
  • Page 7 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:38 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 8 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:38 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 9 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:38 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 10 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:38 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 11 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:38 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 12 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:38 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 13 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver fin &...
  • Page 14 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver fin &...
  • Page 15 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver fin &...
  • Page 16 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:33 Lo:31 × × – Starting method – Direct line start Louver fin &...
  • Page 17 Model FDT100VNV Model FDT100VNV Item FDT100V FDC100VN Nominal cooling capacity 10.0 [4.0~11.2] Nominal heating capacity 11.2 [4.0~12.5] Power source 1 Phase, 220-240V 50Hz/220V 60Hz Cooling power consumption 2.76/2.76 Running current (Cooling) 12.1/12.7 Power factor (Cooling) 99/99 Heating power consumption 2.74/2.74 Running current (Heating) 12.0/12.6 Power factor (Heating)
  • Page 18 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:40 Me:37 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 19 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:40 Lo:37 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 20 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:42 Me:40 Lo:37 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 21 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:43 Me:41 Lo:38 × × – Starting method – Direct line start Louver fin &...
  • Page 22 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:43 Me:41 Lo:38 × × – Starting method – Direct line start Louver fin &...
  • Page 23 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver f in &...
  • Page 24 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver fin &...
  • Page 25 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:31 × × – Starting method – Direct line start Louver fin &...
  • Page 26 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 27 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 28 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:33 Lo:31 × × – Starting method – Direct line start Louver fin &...
  • Page 29 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:33 Lo:31 × × – Starting method – Direct line start Louver fin &...
  • Page 30 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:40 Me:37 Lo:35 × × – Starting method – Direct line start Louver fin &...
  • Page 31 Model FDT250VSPV (Indoor unit: 2 units, Outdoor unit: 1 unit) FDT250VSPV Model Item FDT125V FDC250VS Nominal cooling capacity 25.0 [10.0~28.0] Nominal heating capacity 28.0 [9.5~31.5] Power source 3 Phase, 380-415V 50Hz/380V 60Hz Cooling power consumption 8.30/7.75 Running current (Cooling) 12.8/13.4 Power factor (Cooling) 94/94 Heating power consumption...
  • Page 32 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver fin &...
  • Page 33 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver fin &...
  • Page 34 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:33 Lo:31 × × – Starting method – Direct line start Louver fin &...
  • Page 35 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 × × – Starting method – Direct line start Louver fin &...
  • Page 36 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:33 Me:31 Lo:30 Cooling:57, Heating: 58 × × – Starting method –...
  • Page 37 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:39 Me:38 Lo:37 × × – Starting method – Direct line start Louver fin &...
  • Page 38 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:39 Me:38 Lo:37 × × – Starting method – Direct line start Louver fin &...
  • Page 39 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:41 Me:39 Lo:38 × × – Starting method – Direct line start Louver fin &...
  • Page 40 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:41 Me:39 Lo:38 × × – Starting method – Direct line start Louver fin &...
  • Page 41 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:44 Me:41 Lo:39 × × – Starting method – Direct line start Louver fin &...
  • Page 42 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:44 Me:41 Lo:39 × × – Starting method – Direct line start Louver fin &...
  • Page 43 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:46 Me:44 Lo:43 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 44 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:46 Me:44 Lo:43 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 45 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:46 Me:44 Lo:43 × × – Starting method – Direct line start Louver fin &...
  • Page 46 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:46 Me:44 Lo:43 × × – Starting method – Direct line start Louver fin &...
  • Page 47 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:39 Me:38 Lo:37 × × – Starting method – Direct line start Louver fin &...
  • Page 48 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:39 Me:38 Lo:37 × × – Starting method – Direct line start Louver fin &...
  • Page 49 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:39 Me:38 Lo:37 × × – Starting method – Direct line start Louver fin &...
  • Page 50 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:41 Me:39 Lo:38 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 51 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:41 Me:39 Lo:38 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 52 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:41 Me:39 Lo:38 × × – Starting method – Direct line start Louver fin &...
  • Page 53 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:41 Me:39 Lo:38 × × – Starting method – Direct line start Louver fin &...
  • Page 54 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:44 Me:41 Lo:39 × × – Starting method – Direct line start Louver fin &...
  • Page 55 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:46 Me:44 Lo:43 Cooling:57, Heating:58 × × – Starting method – Direct line start Louver fin &...
  • Page 56 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:39 Me:38 Lo:37 × × – Starting method – Direct line start Louver fin &...
  • Page 57 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:39 Me:38 Lo:37 × × – Starting method – Direct line start Louver fin &...
  • Page 58 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:41 Me:39 Lo:38 × × – Starting method – Direct line start Louver fin &...
  • Page 59 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 × × – Starting method – Direct line start Louver fin &...
  • Page 60 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 × × – Starting method – Direct line start Louver fin &...
  • Page 61 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:32 Lo:29 × × – Starting method – Direct line start Louver fin &...
  • Page 62 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:37 Me:35 Lo:32 × × – Starting method – Direct line start Louver fin &...
  • Page 63 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:37 Me:35 Lo:32 × × – Starting method – Direct line start Louver fin &...
  • Page 64 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:38 Me:36 Lo:33 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 65 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:38 Me:36 Lo:33 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 66 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:38 Me:36 Lo:33 × × – Starting method – Direct line start Louver fin &...
  • Page 67 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:38 Me:36 Lo:33 × × – Starting method – Direct line start Louver fin &...
  • Page 68 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 × × – Starting method – Direct line start Louver fin &...
  • Page 69 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 × × – Starting method – Direct line start Louver fin &...
  • Page 70 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 71 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 Cooling: 50, Heating: 51 × × – Starting method –...
  • Page 72 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:32 Lo:29 × × – Starting method – Direct line start Louver fin &...
  • Page 73 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:32 Lo:29 × × – Starting method – Direct line start Louver fin &...
  • Page 74 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:37 Me:35 Lo:32 × × – Starting method – Direct line start Louver fin &...
  • Page 75 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:38 Me:36 Lo:33 Cooling:57, Heating:58 × × – Starting method – Direct line start Louver fin &...
  • Page 76 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 × × – Starting method – Direct line start Louver fin &...
  • Page 77 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:34 Me:31 Lo:28 × × – Starting method – Direct line start Louver fin &...
  • Page 78 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi:35 Me:32 Lo:29 × × – Starting method – Direct line start Louver fin &...
  • Page 79 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi: 41, Lo: 37 × × – Starting method – Direct line start Louver fin &...
  • Page 80 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi: 42, Lo: 37 × × – Starting method – Direct line start Louver fin &...
  • Page 81 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi: 42, Lo: 37 × × – Starting method – Direct line start Louver fin &...
  • Page 82 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi: 43, Lo: 38 Cooling:50, Heating:51 × × – Starting method –...
  • Page 83 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi: 42, Lo: 38 Cooling:50, Heating:51 × × – Starting method –...
  • Page 84 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi: 43, Lo: 38 × × – Starting method – Direct line start Louver fin &...
  • Page 85 Model Item Cooling power consumption Running current (Cooling) Power factor (Cooling) Heating power consumption Running current (Heating) Power factor (Heating) Inrush current (L.R.A) <Max. running current> Noise level dB(A) Hi: 43, Lo: 38 × × – Starting method – Direct line start Louver fin &...
  • Page 86 Model FDU200VSV FDU200VSV Model Item FDU200V FDC200VS Nominal cooling capacity 20.0 [7.0~22.4] Nominal heating capacity 22.4 [7.6~25.0] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 6.59/6.58 Running current (Cooling) 10.8/11.4 Power factor (Cooling) 88/88 Heating power consumption 6.08/5.84 Running current (Heating) 10.2/10.3 86/86...
  • Page 87 Model FDU250VSV FDU250VSV Model Item FDU250V FDC250VS Nominal cooling capacity 25.0 [10.0~28.0] Nominal heating capacity 28.0 [9.5~31.5] Power source 3 Phase, 380–415V 50Hz/380V 60Hz Cooling power consumption 9.91/10.21 Running current (Cooling) 15.7/17.0 Power factor (Cooling) 91/91 Heating power consumption 8.50/8.22 Running current (Heating) 14.4/14.7 85/85...
  • Page 88 1.2.2 Range of usage & limitations See the next page. When used below -5 , install a snow hood(option).<71 250 only> Considering to get sufficient heating capacity, the area where the averaged lowest ambient air temperature in day time during winter is above 0 , and it has no accumulation of snow.
  • Page 89 Operating temperature range Models 40 Cooling Usage range in cooling Indoor air temperature Heating Usage range in heating Outdoor air temperature Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in places where natural wind can increase or decrease its design airflow rate. PCA001Z561 “CAUTION”...
  • Page 90 PCA001Z561...
  • Page 91 PCA001Z561 89-1...
  • Page 92 Unit:mm Ducting for Decorative panel air outlet 530 (Suspension bolts pitch) Control Air return Air supply grille Drain hose piece (Accessory) Opening for exit wiring (Installed on site) Drain (Connectable with VP20) Liquid piping ø6.35(1/4") Suspension bolts 295~325 Gas piping (M10 or M8) ø12.7(1/2") Hanger plate for...
  • Page 93 Unit:mm...
  • Page 95 (c) Duct connected-Middle static pr essure-type (FDUM) Model FDUM 50V Unit : mm 660 (Duct dimension) Space for installation and service Hole for wiring Inspection hole Drain hose piece (Accessory) (Installed on site) 12-ø4 Holes for Return air duct tapping screw Notes (1) The model name label is attached on the lid of the control box.
  • Page 96 Models FDUM60V, 71V Unit : mm Space for installation and service 860 (Duct dimension) Hole for wiring 4 × 200 = 800 Inspection hole Drain hose piece (Accessory) (Installed on site) Return air duct 14-ø4 Holes for Notes (1) The model name label is attached on the lid on tapping screw the lid of the control box.
  • Page 97 Models FDUM100V, 125V, 140V Unit : mm Space for installation and service 1280 (Duct dimension) Inspection 6 × 200 = 1200 hole Hole for wiring Drain hose piece (Accessory) (Installed on site) 18-ø4 Return Air duct Holes for tapping screws Notes (1) The model name label is attached on the lid of the control box.
  • Page 98 (d) Duct connected-High Static pressure-type (FDU) Model FDU71V Unit : mm Space for installation and service (Suspension bolts pitch) 1200 Inspection hole Notes (1) The model name label is attached on the lid of the control box. (2) Prepare the connecting socket (VP20)on site. Control box Drain hose piece Gas piping...
  • Page 99 Models FDU100V, 125V, 140V Unit : mm (Suspension bolts pitch) Space for installation and service 1370 1720 Inspection hole Notes (1) The model name label is attached on the lid of the control box. (2) Prepare the connecting socket (VP20)on site. Control box Gas piping Drain hose piece...
  • Page 100 Unit : mm...
  • Page 101 Unit : mm Holes suspension bolts (M10 or M8) 290(Suspension bolts pitch) Liquid piping Gas piping Drain hose piece (Accesory, 0.3m) 1070 (Installed on site) Air supply Drain hose Receiving part (VP20) Note (1) The slope of drain piping inside the unit must take decline of 10mm.
  • Page 102 Unit : mm...
  • Page 103 Unit : mm...
  • Page 104 Unit : mm Wall Wire (Recessed) LCD display Electrical box (Locally Purchased) Cut off with a knife or the like thin walled parts intend- Remote controller ed for screw holes, and then outline fix it with screws. For the passage Attachment hole after wiring 9 4.5 Long hole(4 pcs.)
  • Page 105 Unit: mm...
  • Page 107 Unit: mm...
  • Page 108 Unit: mm...
  • Page 109 Unit: mm...
  • Page 110 Unit: mm...
  • Page 111 × Plaster white Light gray Light gray (Vertical louver) Plaster white Plaster white (Horizontal louver) (Side panel) (Front panel) Plaster white (Front panel) Plaster white (Air return grille)
  • Page 112 Stucco white Stucco white Stucco white...
  • Page 113 Cooling cycle Heating cycle Check joint Gas line (ø12.7) Service valve Thermistor (Flare connecting) Heat exchanger -R3) 4way valve Heat exchanger Muffler Thermistor Thermistor (Outdoor air temp.) Thermistor (Discharge (TH2) pipe temp.) (TH3) Discharge Compressor Strainer Thermistor (Heat exchanger Suction pipe temp.) Thermistor (TH1)
  • Page 114 Models 100, 125,140 Indoor unit Outdoor unit Cooling cycle Heating cycle Check joint 4way valve Thermistor Gas line ( 15.88) Thermistor Service valve -R3) (Flare connecting) Check joint Heat exchanger Heat exchanger High pressure Check switch valve Thermistor 63H1 Muffler Lower pressure sensor Thermistor Thermistor...
  • Page 115 Cooling cycle Heating cycle Gas branch pipe Check joint Thermistor Check joint Gas line Low pressure Muffler sensor (PSL) Service valve 4way valve Flare connecting (Flare connecting) Thermistor Thermistor High pressure -R3) switch Thermistor Heat (63H1) Heat exchanger exchanger Check valve Thermistor -R1) Muffler...
  • Page 116 Models 200,250 Gas branch pipe ( 15.88) Outdoor unit Indoor unit Indoor unit Cooling cycle Heating cycle Check joint 4way valve Thermistor Gas line ( 22.22) Muff Service valve Flare connecting (Flare connecting) Check joint High pressure Thermistor Lower pressure switch sensor -R3)
  • Page 117 Model 200 Gas branch pipe ( 15.88) Cooling cycle Heating cycle Indoor unit Indoor unit Indoor unit Outdoor unit Check joint 4way valve Thermistor Gas line ( 22.22) Muff Flare connecting Service valve (Flare connecting) Check joint Thermistor High pressure Lower pressure -R3) switch...
  • Page 118 (4) Double twin type Models 200, 250 2nd branch pipe of gas ( 15.88) Cooling cycle Heating cycle 1nd branch Outdoor unit Indoor unit Indoor unit pipe of gas Check joint 4way valve Thermistor Gas line ( 15.88) Thermistor Muff ( 22.22) -R3) Service valve...
  • Page 119 OFF 63˚C ON 56˚C Indoor unit OFF 1.0˚C ON 10˚C OFF 53˚C OFF 51˚C Outdoor unit ON 63˚C ON 65˚C OFF 105˚C OFF 115˚C OFF 135˚C Outdoor unit ON 95˚C ON 85˚C ON 90˚C OFF 4.15MPa Outdoor unit — ON 3.15MPa OFF 0.227MPa Outdoor unit —...
  • Page 120: (A) Ceiling Cassette-4Way Compact (600 600Mm) Type (Fdtc)

    (1) Capacity tables (a) Ceiling cassette-4way compact (600 600mm) type (FDTC) 1) Single type Indoor unit air flow(Standard) Model FDTC40ZHXV Indoor unit FDTC40V Outdoor unit SRC40ZHX-S AF: 11.5 CMM BF: 0.08...
  • Page 121: (B) Ceiling Cassette-4Way-Type (Fdt)

    FDTC100VNPV Model Indoor unit FDTC50V Outdoor unit FDC100VN Indoor unit air flow(Standard) FDTC100VSPV Model Indoor unit FDTC50V Outdoor unit FDC100VS AF: 23 CMM BF: 0.08 Cool Mode Heat Mode Indoor air temperature Indoor air temperature Outdoor Outdoor air temp. 23 DB 26 DB 27 DB 28 DB...
  • Page 122 Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDT60ZHXV Model Indoor unit FDT60V Outdoor unit SRC60ZHX-S AF: 18 CMM BF: 0.11 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature Outdoor Outdoor Outdoor...
  • Page 123 FDT140VNV Model Indoor unit FDT140V Outdoor unit FDC140VN Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDT140VSV Model Indoor unit FDT140V Outdoor unit FDC140VS AF: 30 CMM BF: 0.12 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Outdoor Outdoor...
  • Page 124 FDT140VNPV Indoor unit air flow(Standard) Indoor unit air flow(Standard) Model Indoor unit FDT71V Outdoor unit FDC140VN FDT140VSPV Model Indoor unit FDT71V Outdoor unit FDC140VS AF: 42 CMM BF: 0.15 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Outdoor Outdoor...
  • Page 125: (C) Ceiling Suspended Type (Fden)

    Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDT200VSTV Model Indoor unit FDT71V Outdoor unit FDC200VS AF: 63 CMM BF: 0.15 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature Outdoor Outdoor Outdoor...
  • Page 126 Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDEN50ZHXV Model Indoor unit FDEN50V Outdoor unit SRC50ZHX-S AF: 11 CMM BF: 0.15 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Outdoor Outdoor Indoor air temperature Indoor air temperature Outdoor Outdoor...
  • Page 127 FDEN125VNV Model Indoor unit FDEN125V Outdoor unit FDC125VN Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDEN125VSV Model Indoor unit FDEN125V Outdoor unit FDC125VS AF: 29 CMM BF: 0.15 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature...
  • Page 128 FDEN125VNPV Model Indoor unit FDEN60V Outdoor unit FDC125VN Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDEN125VSPV Model Indoor unit FDEN60V Outdoor unit FDC125VS AF: 36 CMM BF: 0.15 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature...
  • Page 129: (D) Duct Connected-Middle Static Pressure-Type (Fdum)

    3) Triple type FDEN140VNTV Model Indoor unit FDEN50V Outdoor unit FDC140VN Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDEN140VSTV Model Indoor unit FDEN50V Outdoor unit FDC140VS AF: 33 CMM BF: 0.15 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature...
  • Page 130 Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDUM71VNV Model Indoor unit FDUM71V Outdoor unit FDC71VN AF: 20 CMM BF: 0.15 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature Outdoor Outdoor Outdoor...
  • Page 131 2) Twin type FDUM100VNPV Indoor unit air flow(Standard) Indoor unit air flow(Standard) Model Indoor unit FDUM50V Outdoor unit FDC100VN FDUM100VSPV Model Indoor unit FDUM50V Outdoor unit FDC100VS AF: 28 CMM BF: 0.11 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature...
  • Page 132 Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDUM250VSPV Model Indoor unit FDUM125V Outdoor unit FDC250VS AF: 68 CMM BF: 0.14 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature Outdoor Outdoor Outdoor...
  • Page 133 FDU100VNV Model Indoor unit FDU100V Outdoor unit FDC100VN Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDU100VSV Model Indoor unit FDU100V Outdoor unit FDC100VS AF: 34 CMM BF: 0.12 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature...
  • Page 134 Indoor unit air flow(Standard) Indoor unit air flow(Standard) FDU250VSV Model Indoor unit FDU250V Outdoor unit FDC250VS AF: 68 CMM BF: 0.13 Cool Mode Cool Mode Heat Mode Heat Mode Indoor air temperature Indoor air temperature Indoor air temperature Indoor air temperature Outdoor Outdoor Outdoor...
  • Page 135 Correction of cooling and heating capacity in relation to air flow rate control (fan speed) High Fan speed 1.00 0.97 0.95 Coefficient Correction of cooling and heating capacity in relation to one way length of refrigerant piping It is necessary to correct the cooling and heating capacity in relation to the one way equivalent piping length between the indoor and outdoor units.
  • Page 136 (4) When the outdoor unit is located below indoor units in cooling mode, or when the outdoor unit is located above indoor units in heating mode, the correction coefficient mentioned in the below table should be subtracted from the value in the above table. Height difference between the indoor unit and outdoor unit in the vertical height difference Adjustment coefficient...
  • Page 137 • External static pressure table How to interpret the blower characteristics table Unit : Pa (50Hz/60Hz) Example : Case of FDUM60V (50Hz) Duct specs. 1 spot Standard Square duct closing Air flow /min) Stan- High Stan- High Stan- High Model speed dard speed...
  • Page 141 Model FDU200V Standard (Factory Settings) High High 50Hz 60Hz Example of duct Example of duct 38 40 Lower Upper Lower Standard Standard Upper limit limit limit limit Air flow(m /min) Air flow(m /min) When the fan controller kit is used (Option) •Standard rating point rated air volume at 100Pa High High...
  • Page 142 Model FDU250V Standard (Factory Settings) High High 50Hz 60Hz Example of duct Example of duct 85 88 Lower Upper Lower Standard Upper Standard limit limit limit limit Air flow(m /min) Air flow(m /min) When the fan controller kit is used (Option) •Standard rating point rated air volume at 100Pa High High...
  • Page 143 Notes (1) The data are based on the following conditions. Ambient air temperature: Indoor unit 27˚C DB, 19˚C WB. Outdoor unit 35˚C DB. Notes (2) The data in the chart are measured in an anechoic room. Notes (3) The noise levels measured in the field are usually higher than the data because of reflection. Notes (4) Noise levels for the FDTC, FDT, FDEN and FDKN series show the noise level when in the Powerful mode.
  • Page 144 Unit Measured based on JIS B 8616 Mike position as pen drawing Mike (in front & below unit) 39 dB (A) at HIGH 41 dB (A) at HIGH 44 dB (A) at HIGH 38 dB (A) at MEDIUM 39 dB (A) at MEDIUM 41 dB (A) at MEDIUM 37 dB (A) at LOW 38 dB (A) at LOW...
  • Page 145 38 dB (A) at HIGH 36 dB (A) at MEDIUM 33 dB (A) at LOW Measured based on JIS Unit B 8616 1.5 m Mike position as pen Mike drawing (at center & below unit) 41 dB (A) at HIGH 42 dB (A) at HIGH 43 dB (A) at HIGH 37 dB (A) at Low...
  • Page 146 Measured based on JIS B 8616 Mike position: at highest noise level in position as mentined below Distance from front side 1m Height 47 dB (A) 47 dB (A) 48 dB (A) 1000 2000 4000 8000 1000 2000 4000 8000 1000 2000 4000...
  • Page 147 ×...
  • Page 158 1.4 OUTLINE OF OPERATION CONTROL BY MICROCOMPUTER (1) Remote controller Wired remote controller The figure below shows the remote controller with the cover opened. Note that all the items that may be displayed in the liquid crystal display area are shown in the figure for the sake of explanation. Characters displayed with dots in the liquid crystal display area are abbreviated.
  • Page 159 Wireless remote controller – –...
  • Page 160 (2) Operation control function by the indoor controller Auto operation [Applicable model: All models of the cooling and heating type] If “Auto” mode is selected by the remote controller, the heating and the cooling are automatically switched according to the difference between outdoor air temperature and setting temperature and the difference between setting temperature and return air temperature.
  • Page 161 Timer operation [Applicable model: All models] Timer Set the duration of time from the present to the time to turn off the air-conditioner. It can be selected from 10 steps in the range from “OFF 1 hour later” to “OFF 10 hours later”. After the clock timer setting, the remaining time is displayed with progress of time in the unit of hour.
  • Page 162 Hot keep [Applicable model: All models of the heating and cooling type] Hot keep control is performed at the start of the defrost control. Control When the indoor heat exchanger temperature (detected with Th -R1 or R2) drops to 35°C or lower, the speed of indoor fan is changed to the lower tap at each setting.
  • Page 163 Automatic louver level setting during heating At the hot start with the heating thermostat OFF, regardless whether the auto swing switch is operated or not (auto swing or louver stop), the louver takes the level position (In order to prevent the cold start). The louver position display LCD continues to show the display which has been shown before entering this control.
  • Page 164 Operation check mode There is no communication with the outdoor unit but it allows performing operation in respective modes by operating the remote controller. Drain pump test run mode As the drain pump test run is established, the drain pump only operates and during the operation protective functions by the microcomputer of indoor unit become ineffective.
  • Page 165 Anomalous fan motor [In case of FDT only] After starting the fan motor, if the fan motor speed is 200rpm or less is detected for 30 seconds continuously and 4 times within 60 minutes, then fan motor stops with the anomalous stop (E16). Plural unit control –...
  • Page 166 Abnormal temperature thermistor (return air/indoor unit heat exchanger) wire/short-circuit detection [Applicable model: All models] Broken wire detection When the return air temperature thermistor detects -20°C or lower or the heat exchanger temperature thermistor detect -40°C or lower for 5 seconds continuously, the compressor stops. After a 3-minute delay, the compressor restarts but, if it is detected again within 60 minutes after the initial detection for 6 minutes continuously, stops again (the return air temperature thermistor: E7, the heat exchanger temperature thermistor: E6).
  • Page 167 Remote operation input Remote operation inputs (switch input, timer input) connectors (CnT) are provided on the indoor control PCB. However, the remote operation by the CnT is not effective when “Center mode” is selected with the air-conditioner. Factory default (At the shipping from factory) [Indoor function of wired remote controller “External input selector”...
  • Page 168 (3) Operation control function by the wired remote controller Switching sequence of the operation mode switches of remote controller [CPU reset] This functions when [Inspection] and [Grill Up/Down] buttons on the remote controller are pressed simultaneously. Operation is same as that of the power supply reset. [Power failure compensation function]...Electric power supply failure •...
  • Page 169 (4) Operation control function by the outdoor controller ◆ SRC40~60 models (a) Outline of heating operation 1) Operation of major functional components in heating mode Heating Thermostat ON Thermostat OFF Defrost Failure Compressor Indoor fan motor ON(HOT KEEP) Outdoor fan motor (few minutes ON) 4-way valve (3 minutes ON)
  • Page 170 (c) Protective control function 1) Frost prevention control (During cooling or dehumidifying) a) Operating conditions Indoor heat exchanger temperature (Th2) is lower than 5ºC. Inverter command ii) 5 minutes after reaching the inverter command speed except 0 rps. speed Lower b) Detail of anti-frost operation limit Indoor heat exchanger...
  • Page 171 4) Cooling low outdoor temperature protective control a) Operating conditions: When the ambient air temperature (Th5) is C ºC or lower continues for 20 seconds while the inverter command speed is other than 0 rps. b) Detail of operation: 1 The lower limit of the inverter command speed is set to 44 (30) rps and even if the speed becomes lower than 44 (30) rps, the speed is kept to 44 (30) rps.
  • Page 172 6) Heating overload protective control a) Operating conditions: When the ambient air temperature (Th5) is 17˚C or higher continues for 30 seconds while the inverter command speed other than 0 rps. b) Detail of operation: 1 Taking the upper limit of inverter command speed range at 50 rps, if the output speed obtained with the fuzzy calculation exceeds the upper limit, the upper limit value is maintained.
  • Page 173 8) Compressor overheat protection a) Purpose: It is designed to prevent deterioration of oil, burnout of motor coil and other trouble resulting from the compressor overheat. b) Detail of operation Speeds are controlled with temperature detected by the sensor mounted on the discharge pipe. (Example) Fuzzy 4 rps After lapse of 3 min.
  • Page 174 12) Serial signal transmission error protection a) Purpose: Prevents malfunction resulting from error on the indoor ↔ outdoor signals. b) Detail of operation: If the compressor is operating and a serial signal cannot be received from the indoor control with outdoor control having serial signals continues for 7 minute and 35 seconds, the com- pressor is stopped.
  • Page 175 FDC 71 - 250 models Determination of compressor speed (frequency) Required frequency Cooling/dehumidifying operation Unit: rps Model Indoor unit air flow “Hi” Max. required frequency Indoor unit air flow “Me”, “Lo” Min. required frequency Heating operation Unit: rps Model Indoor unit air flow “Hi” Max.
  • Page 176 Compressor soft start control Compressor protection start I [Control condition] Normally, the compressor operation frequency is raised in this start pattern. [Control contents] a) Starts with the compressor’s target frequency at A rps. However, when the outdoor air temperature (Tho-A) is 35°C or higher during cooling/ dehumidifying or the indoor return air temperature (Th -A) is 25°C or higher during heating, it starts at C rps.
  • Page 177 Low frequency operation control during heating [Control condition] When the conditions of compressor protection start III are established and one of following conditions is satisfied, the low number of revolutions operation control is performed during heating. At 30 minutes or more after turning the power supply breaker on Compressor underneath temperature (Tho-H) is 4°C or higher and the difference from the outdoor air temperature (Tho-A) becomes 4°C or higher.
  • Page 178 Outdoor unit fan control at cooling low outdoor air When all the following conditions are established after the start of compressor, the following control is implemented. If the outdoor air temperature (Tho-A) is in the zone in the cooling/dehumidifying mode, it has elapsed 20 seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
  • Page 179 Caution at the outdoor unit fan start control When the outdoor unit fan is running at 400min before operating the compressor, it may operate with the compressor only, without starting up the outdoor fan This is normal. Snow protection fan control If the dip switch (SW3-2) on the outdoor unit control PCB is turned ON, the outdoor unit fan is operated for 30 seconds at 4 tap speed once in every 10 minutes depending on the outdoor air temperature (detected with Tho-A) in the stop mode or anomalous stop mode.
  • Page 180 Defrosting end conditions When any of the following conditions is satisfied, the defrosting end operation starts. When it has elapsed 8 minutes and 20 seconds after the start of defrosting. (After 10 minutes and 20 seconds for model 71, 200 and 280) When the outdoor unit heat exchanger temperatures (Tho-R1, R2), whichever the lower, becomes 12°C or higher for 10 seconds continuously.
  • Page 181 Heating high pressure protection Protective control As the indoor unit heat exchanger temperature (Th -R) exceeds the setting value, the compressor speed (frequency) is controlled to suppress the rise of high pressure. ii) Control value A is updated to an optimum value automatically according to the operating conditions. Existing piping adaptation switch: SW5-1 (SW8-1: model 80) Model OFF (Shipping)
  • Page 182 Over-current protection current safe controls I, II Detecting the outdoor unit inverter input (primary) current and the output (secondary) current, if the current values exceed setting values, the compressor speed (frequency) is controlled to protect the inverter. Cooling Heating Model Control Reset value Control...
  • Page 183 13) Dewing prevention control [Control condition] During cooling and dehumidifying operation, if all the following conditions are established, the compressor speed (frequency) is reduced to prevent dewing and water splash. Cooling electronic expansion valve aperture (EEVC) is 500 pulses. Suction overheat is 10°C or higher. Compressor speed (frequency) is A rps or higher.
  • Page 184 Silent mode As “Silent mode start” signal is received from the remote controller, it operates by dropping the outdoor unit fan tap and the compressor speed (frequency). For details, refer to items (a) and (d) above. Test run It is possible to operate from the outdoor unit using the dip switch on the outdoor unit control PCB. Cooling test run SW3-4 SW3-3...
  • Page 185: Application Data

    1.5 APPLICATION DATA SAFETY PRECAUTIONS Read the “SAFETY PRECAUTIONS” carefully first of all and then strictly follow it during the installation work in order to protect yourself. The precautionary items mentioned below are distinguished into two levels, WARNING and CAUTION . WARNING : Wrong installation would cause serious consequences such as injuries or death.
  • Page 186 ¡ Make sure there is no dust or clogging on both the plug and the socket nor loose connection of the socket before plugging, and plug in securely to the end of the blade. Accumulation of dust, clogging on the socket or plug, or loose installation of the socket could cause electric shock and fire.
  • Page 187 ¡ Do not install the indoor unit at the place listed below. • Places where flammable gas could leak. • Places where carbon fiber, metal powder or any powder is floated. • Place where the substances which affect the air conditioner are generated such as sulfide gas, chloride gas, acid or alkali.
  • Page 188: Installation Of Indoor Unit

    1.5.1 Installation of indoor unit Ceiling cassette-4 way compact (600×600mm)-type (FDTC) Selection of installation location 1) Select location where the space above ceiling is larger than those mentioned below and perfect draining can be assured. 2) With the customer’s consent, select a location with following suitable conditions. a) Where cool air or hot air can easily pass through.
  • Page 189 • Please arrange four sets of a suspension bolt (M10 or M8), a nut matching the bolt, a flat washers and a spring washer on the installation site. This unit is designed for installation on a 2 × 2 grid ceiling. If necessary, please detach the T bar temporarily before you install it.
  • Page 190 3) Care must be taken so as not to allow an adhesive to run into the drain hose. When it is hardened, it can cause a breakage of a flexible part, if the flexible part receives stress. 4) Use VP-20 general-purpose hard PVC pipes for drain piping. 5) Insert the drain hose supplied as an accessory (soft PVC end) to the stepped part of the unit’s drain socket and then fasten it with the clamp also supplied as an ac- cessory.
  • Page 191 Setup from a remote controller side. Drain pump operation from remote control unit is possible. Operate a remote control unit by following the steps described below. Press the button for three seconds or longer. The display will change “ ” Press the button once and cause “...
  • Page 192 7) A panel is hooked on two bolts ( mark ) [Figure 4] 8) Please rotate a hook, put in the slot on the panel, and carry out fixing the panel temporarily. [Figure 5] 9) Tighten the two bolts used for fixing the panel temporarily and the other two. 10) Please open the lid of a control box.
  • Page 193: Ceiling Cassette-4Way-Type (Fdt)

    (2) Ceiling cassette-4way-type (FDT) (a) Selection of installation location for the indoor unit q Select the suitable areas to install the unit under approval of the user. • Areas where the indoor unit can deliver hot and cold wind sufficiently. Suggest to the user to use a circulator if the ceiling height is over 3m to avoid warm air being accumulated on the ceiling.
  • Page 194 (b) Preparation before installation If suspension bolt becomes longer, do reinforcement of earthquake resistant. For grid ceiling When suspension bolt length is over 500mm, or the gap between the ceiling and roof is over 700mm, apply earthquake resistant brace to the bolt. In case the unit is hanged directly from the slab and is installed on the ceiling plane which has enough strength.
  • Page 195 (c) Installation of indoor unit Work procedure 1) Prepare a ceiling hole with the size of from 860mm 860mm to 910mm 910mm referring to the template attached in the package. 2) Arrange the suspension bolt at the right position (725mm 778mm).
  • Page 196 (e) Refrigerant pipe Caution Use the new refrigerant pipe. When re-using the existing pipe system for R22 or R407C, pay attention to the following items. • Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts. •...
  • Page 197 Drain pipe Caution Install the drain pipe according to the installation manual in order to drain properly. Imperfection in draining may cause flood indoors and wetting the household goods, etc. Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the other harmful andinflammable gas is generated.
  • Page 198 4) Insulate the drain pipe. Be sure to insulate the drain socket and rigid PVC pipe installed indoors otherwise it may cause dew condensation and water leakage. ❈ After drainage test implementation, cover the drain socket part with pipe cover (small size), then use the pipe cover (big size) to cover the pipe cover (small size), clamps and part of the drain hose, and fix and wrap it with tapes to wrap and make joint part gapless.
  • Page 199 (h) Wiring-out position and wiring connection Electrical installation work must be performed according to the installation manual by an electrical installation service provider qualified by a power provider of the country, and be executed according to the technical standards and other regulations applicable to electrical installation in the country.
  • Page 200 Panel installation 1) Before installation Follow installation manual carefully, and install the panel properly. Check the following items. Accessories Accessories Bolt 4 pieces For panel installation Strap 4 pieces For avoiding the corner panel from falling Note: Accessories are laid in the position removing the corner panel. ccessories holding position 2) Checking the indoor unit installation position Read this manual together with the air conditioner installation manual carefully.
  • Page 201 6) Attaching the panel a) Temporary attaching Lift up the hanger (2 places) on the panel for temporary support. Hang the panel on the hook on the indoor unit. nitÕs hook Hook hanger PanelÕs fixing hanger b) Fix the panel on the indoor unit Fasten the panel on the indoor unit with the four bolts supplied with the panel.
  • Page 202 7) Electrical wiring a) After removing three screws of control box, detach the cover of control box (the hatched part). b) Connect the connector for louver motor (white 20P). Hold the wiring by using the clamps of the indoor unit. Hold the connector inside the control box.
  • Page 203 Caution Any automatic control or operation from the remote controller will be disabled on the louver whose position is fixed in the above way. Do not set a louver beyond the specified range. Failure to observe this instruction may result in dripping, dew condensation, the fouling of the ceiling and the malfunctioning of the unit.
  • Page 204 1) A place where good air circulation and delivery can be obtained. Unit : m Model Air throw Conditions Installation height: 2.4 ~ 3.0 m above the floor Fan speed: Hi Location: Free space without obstacles Distance of reach indicates the horizontal distance after the wind touched down the floor. Air velocity at the throw: 0.5 ( m/sec.) 2) A place where ceiling has enough strength to support the unit.
  • Page 205 a) Please operate remote control unit switches with the unit faced correctiy toward the indoor unit’s receiver section. b) Effective operation distance can vary with the luminance around the receiver and the reflection from walls of the room. c) When the receiver is exposed to intensive light such as from the Receivable range Receivable range direct sun or a strong light, it may become operable only from a...
  • Page 206 Keep strictly to the suspension bolt lengths speci- fied below. Unit : mm Air supply Model Ceiling board FDEN40, 50 1070 1022 Lug for 1320 1272 FDEN60, 71 suspension 1620 1572 FDEN100, 125, 140 Suspension bolts Wall <If there is ceiling material> <If there is no ceiling material>...
  • Page 207 Piping can be connection from 3 different directions. Remove the cutout from hole where the piping will be connected using side cutters or similar tool. Cut a hole for the piping connection in the back cover according to the cutting margin shown. Cut a hole in the ceiling side in accordance with the position of the piping.
  • Page 208 1) Avoid installation and use at those places listed below. a) Places exposed to oil splashes or steam (e.g. kitchens and machine plants). Installation and use at such places will incur deteriorations in the performance or corrosion with the heat exchanger or damage in molded synthetic resin parts.
  • Page 209 Suspension bolt M10 Suspension bolt M10 nuts M10 Washer Indoor unit Indoor unit M10 Spring washer Adjust the out-levelness using a level vial or by the following method. • Make adjustment so that the relation between the lower surface of the indoor unit proper and water level in the hose becomes given below.
  • Page 210 • When shipped, the return air port lies on the back. • When connecting the duct to the return air port, remove the air filte if it is fitted to return air port. • When placing the return air port to carry out suction from the bottom side, use the following procedure to replace the return air duct joint and the bottom plate.
  • Page 211 • There is a possibility that the supply air volume may exceed the allowable range of operation due to the capacity of ventilation fan or strength of wind blowing against external air louver so that drainage from be heat exchanger may fail to reach the drain pan leak outside (e.g.
  • Page 212 When connecting the drain pipe to the unit, pay sufficient attention not to apply excess force to the piping on the unit side. Also, fix the piping at a point as close as possible to the unit. Level difference part For drain pipe, use hard PVC general purpose pipe VP-20 Drain socket Drain hose...
  • Page 213 Setup from a unit side. In case electrical wiring work finished Drain pump can be operated by remote controller (wired). For the operation method, refer to Operation for drain pump in the installation manual for wiring work. In case electrical wiring work not finished Drain pump will run continuously when the dip switch “SW7-1”...
  • Page 214 (5) Duct connected-High static pressure-type (FDU) Model FDU 71V ~ 140V (a) Selection of installation location 1) Select the suitable areas to install the unit under approval of the user. • Areas where the indoor unit can deliver hot and cold wind sufficiently. Suggest to the user to use a circulator if the ceiling height is over 3m to avoid warm air being accumulated on the ceiling.
  • Page 215: Installation Of Outdoor Unit

    Suspension bolt location Unit: mm Model 100, 125, 140 Mark 1406 Suspension bolt (M10) dhere to the measurements given Unit below for the length of the suspension bolts. Pipe locations Unit: mm Model: FDU71V Models: FDU100V ~ 140V Liquid Liquid piping piping piping...
  • Page 216 (d) Duck Work A corrugated board (for preventing sputtering) is attached to the main body of the air conditioner (on the outlet port). Do not remove it until connecting the duct. The air conditioner main unit does not have an air filter. Incorporate it into the easy-to-clean return air grille. Supply air duct The ducts should be at their minimum lengths.
  • Page 217 (e) Refrigerant pipe Caution Use the new refrigerant pipe. When re-using the existing pipe system for R22 or R407C, pay attention to the following items. • Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts. •...
  • Page 218 Drain pipe Caution Install the drain pipe according to the installation manual in order to drain properly. Imperfection in draining may cause flood indoors and wetting the household goods, etc. Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the other harmful and inflammable gas is generated.
  • Page 219 As wide as possible When sharing a drain pipe for more than one unit, lay (about100mm) the main pipe 100mm below the drain outlet of the unit. In addition, select VP-30 or bigger size for main drain pipe. VP-30 or bigger escending slope greater than 1/100 4) Insulate the drain pipe.
  • Page 220 onnecting port of top drain pipe Outline of bottom drain piping work If the bottom drain piping can be done with a descending gradient (1/50-1/100), it is possible to connect the pipes as shown in the drawing Standard hard polyvinyl chloride pipes below.
  • Page 221 ♦ Model FDU200V, 250V (a) Selection of installation location 1) Install the unit at a place as shown below and which meets the conditions as shown by the following table. Top view Front view Service space All Series Slab Unit : mm Min.
  • Page 222 Four pieces of packing hardware are When delivering the package, move Secure the hanging bolts by either one used. the package to the installation as close of following methods. Discard them after unpacking. as possible. Steel reinforcement When it is unpacked and then moved After removing the hardware, Packing hardware (4 pcs.) to the installation place, sufficient care...
  • Page 223 In the following method, it is assumed that the friction resistance per unit length of duct is 1 Pa/m (0.1 mm Aq/m) and a side of duct is 250 mm. Duct form Square duct Air volume rating is assumed to be FDU250V. Item Dimensions volume...
  • Page 225 2 Install the lower case to the flat wall with attached two wooden screws. Avoid the following locations (a) Direct sunlight. (b) Close to heating device. (c) Highly humid or water splashing area. (d) Uneven surface. (a) Open the cover of remote controller , and remove the screw under the buttons without fail.
  • Page 238 230-1...
  • Page 239 230-2...
  • Page 240 230-3...
  • Page 241 230-4...
  • Page 242 (5) Instructions for branching pipe set installation for Twin/Triple/W-twin configuration systems For R410A PSB012D865 WARNING / CAUTION This set is for R410A refrigerant. Select a branching pipe set correctly rated for the combined total capacity of connected indoor units and install it according to this manual. An improperly installed branching pipe set can cause degraded performance or an abnormal unit stop.
  • Page 243 2. Pipe connecting procedure Braze the different diameter pipe joint found in the set matching the connected outdoor and indoor unit capacities according to the instructions set out below. In connecting an indoor unit of which capacity is 1.5HP, 2HP or 2.5HP always use a 9.52 liquid pipe to connect to the branching CAUTION pipe (branching pipe - indoor unit).
  • Page 244: Outdoor Unit

    2-5 Triple type for same model/same capacity or different model/same capacity When the difference in length of pipes after the branch is longer than 3 m and shorter than 10 m. Outdoor unit model Indoor unit model Branching pipe Branching pipe set type Liquid branching pipe Gas branching pipe Flare joint...
  • Page 245 2-7. W-twin type Pipes should be connected as follows for a W-twin installation (4 connected indoor units. Yhe capacity of an outdoor unit availble for this configuration is either 8HP or 10HP only): Branching pipe Outdoor unit model Liquid branching pipe Gas branching pipe Outdoor unit capacity Indoor unit capacity...
  • Page 246: Method For Connecting The Accessory Pipe (Models Fdc200,250 Only)

    PSB012D917C (6) Method for connecting the accessory pipe (Models FDC200,250 only) Be sure to use the accessory pipe to connect the operation valve on the gas side with the field pipe. Referring to Table and Table , prepare the straight pipe and the elbow in the field, ID22.22 which are used in the construction examples applicable to the connecting direction.
  • Page 247 Accessory pipe A Accessory pipe A Straight pipe (Procured in the field Straight pipe 185~235mm) (Procured in the field above 415mm) Straight pipe (Procured in the field above 125mm) Elbow procured in the field Braze the field pipe here . Braze the field pipe here.
  • Page 248: Wiring Diagram

    Delete Wiring diagram This diagram shows wiring for a 3 phase model. Earth leakage breaker Circuit breaker For twin For triple For double L2 L3 N units units twin units Outdoor unit 2/N 3 2/N 3 2/N 3 2/N 3 Indoor unit Master Slave a...
  • Page 249 2) Set the same address for the master and slave indoor units as the communications address for the remote controller using rotary switch SW2 on the indoor units’ control PCB. 3) Set slave a, slave b and slave c using DIP switch SW5-1 and SW5-2 on the control PCB of the respective indoor slave units. 4) Be sure to press the AIR CON No.
  • Page 250: Setting Functions Using The Wired Remote Controller

    (8) Setting functions using the wired remote controller (a) The initial function setting for typical using is performed automatically for a remote control unit and an indoor unit by the outdoor unit connected, when remote controller and inside unit are connected. As long as they are used in a typical manner, there wiil be no need to change the initial settings.
  • Page 251 2 Indoor unit functions (I/U FUNCTION Note1: Fan setting of "HIGH SPEED" Indoor unit air flow setting Fan tap Only when plural indoor units are connected STAN DAR D HI-MID-LO HI-LO HI- MID Indoor No. selection (Indoor unit function) SPEED (Note3) Function setting...
  • Page 252 (d) How to set function Operation message Stop air-conditioner and press (SET) (MODE) Function description: Function No. setting description: buttons at the same time for over three seconds, and the "FUNCTION SET " will be displayed. Fixing button Press ( SET) button. Make sure which do you want to set, "...
  • Page 253 (d) The range of temperature setting. When shipped, the range of set temperature differs depending on the operation mode as below. Heating : 16~30°C (55~86°F) Except heating (cooling, fan, dry, automatic) : 18~30°C (62~86°F) 1) Upper limit and lower limit of set temperature can be changed with remote controller. Upper limit setting: valid during heating operation.
  • Page 254 (e) Trail operation of drain pump Drain pump operation from remote control unit is possible. Operate a remote control unit by following the steps described below. 1) To start a forced drain pump operation. 1 Press the button for three seconds or longer. The display will change “...
  • Page 255 4) Press button. (selection of louver No.) Select the louver No. to be set according to the right figure. [EXAMPLE] ” ⇔ “ ” ⇔ “ ” ⇔ “ “ ” For FDTC series, set louver No.1 other settings selected have no effect. 5) Press SET button.
  • Page 256 10) Press button. Louver adjusting mode ends and returns to the original display. Caution If the upper limit position number and the lower limit position number are set to the same position, the louver is fixed at that position auto swing does not funtion. ATTENTON If you press RESET button during settings, the display will return to previous display.If you press...
  • Page 257 (ii) FDE series It is possible to change the movable range of the louver on the air supply from the wired remote controller. Once the top and bottom position is set, the louver will swing within the range between the top and the bottom when swing operation is chosen.
  • Page 258 7) Press SET button. (Fixing of the upper limit position) The upper limit position is fixed and the setting position is displayed for two seconds.Then proceed to lower limit position selection display. [EXAMPLE] (displayed for two seconds) (shows current setting) 8) Press button.
  • Page 259 (9) Troubleshooting The operation data is saved when the situation of abnormal operation happen, and the data can be confirmed by remote controller. Error Code of indoor unit [Operating procedure] Display on LED on indoor circuit board remote Content red (checking) green (normal) controller (a) Press the...
  • Page 260 Pressing the button will stop displaying data. Pressing the (RESET) button during remote control unit operation will undo your last operation and allow you to go back to the previous screen. If two (2) remote controllers are connected to one (1) indoor unit, only the master controller is available for trial operation and confirmation of operation data.
  • Page 261 Delete...
  • Page 262: Maintenance Data

    1.6 MAINTENANCE DATA 1.6.1 Servicing Evacuation The evacuation is a procedure to purge impurities, such as noncondensable gas, air, moisture from the refrigeration circuit by using a vacuum pump. Since the refrigerant R410A is very insoluble in water, even a small amount of moisture left in the refrigeration circuit will freeze, causing what is called ice clogging.
  • Page 263: Trouble Shooting For Refrigerant Circuit

    Refrigerant charging After the evacuation shown in the above, change the connection of the charge hose to the refrigerant cylinder. (b) Purge air from the charge hose First loosen the connecting portion of the charge hose at the gauge manifold side and open valve for a few seconds, and then immediately retighten it after observing that gas has blown out from loosened connecting portion.
  • Page 264: Diagnosing Of Microcomputer Circuit

    1.6.3 Diagnosing of microcomputer circuit Selfdiagnosis function (a) Check Indicator Table Whether a failure exists or not on the indoor unit and outdoor unit can be know by the contents of remote controller error code, indoor/outdoor unit green LED (power pilot lamp and microcomputer normality pilot lamp) or red LED (check pilot lamp). Indoor unit side Remote controller Indoor unit control PCB Outdoor unit control PCB...
  • Page 265 (ii) Outdoor unit side Model SRC40~60 Indoor unit control Outdoor unit Remote controller control PCB Location of Reference Description of trouble Repair method Error trouble page Red LED Red LED Green LED Red LED code Keeps Stays OFF 1 time flash Power supply wires • Anomalous current on inverter primary side Repair flashing Installation,...
  • Page 266 Model FDC71~250 Remote controller Indoor unit control PCB Outdoor unit control PCB Reference Location of trouble Description of trouble Repair method Green Green page Error code Red LED Red LED Red LED LED (1) LED (1) • Outdoor unit power supply L3-phase interruption, defective noise filter Power supply wires Repair (3-phase model only)
  • Page 267 (iv) Display sequence of error codes or inspection indicator lamps Occurrence of one kind of error Displays are shown respectively according to errors. Occurrence of plural kinds of error Section Category of display Error code on remote • Displays the error of higher priority (When plural errors are persisting) controller Red LED on indoor unit control PCB...
  • Page 268: Troubleshooting Procedure

    Resetting the error log • Resetting the memorized error log in the remote controller Holding down “CHECK” button, press “TIMER” button to reset the error log memorized in the remote controller. • Resetting the memorized error log The remote controller transmits error log erase command to the indoor unit when “VENTI” button is pressed while holding down “CHECK”...
  • Page 269 Model: FDT, FDTC series • Control PCB This PCB is for spare part that must be set up according to following instruction since it is common. Set to an appropriate address and function by using switch on PCB. Select the same setting with the removed PCB. item switch Content of control...
  • Page 270 • Power PCB This PCB is for spare part that must be set up according to following instruction since it is common. Replace the PCB 1. Fix the PCB so as not to pinch the wirings. 2. Be sure to connect the connectors with same color of the PCB connectors. Power PCB The parts mounted on PCB are different with respect to each PCB.
  • Page 271 Model: FDUM, FDDU, FDEN series item switch Content of control Set an appropriate address and Master/Slave setting by using dip switches. Address Plural indoor units control by 1 remote controller Set the same setting with the PCB removed from the unit. Master Slave1 Slave2...
  • Page 272 DIP switch setting list (Indoor unit) Indoor unit (FDTC,FDT,FDEN,FDUM,FDU) Switches Description Default setting Remarks Address No. setting at plural indoor units control by 1 R/C SW5-1 Master/Slave setting Master /Slave See table 2 SW5-2 SW6-1 SW6-2 Model selection As per model See table 1 SW6-3 SW6-4...
  • Page 273: Troubleshooting At The Outdoor Unit Side

    Troubleshooting at the outdoor unit side When troubleshooting the outdoor unit, firstly assess the overview of malfunction and try to presume the cause and the faulty part by checking the error cord dispalyed on the remote controller and flashing pattern of indicator lamps (Red LED and Green LED), and then proceed further inspection and remedy it.
  • Page 274 140VN Model FDC100VN, 125VN, Replace the PCB after elapsing 3 minutes from power OFF. (Be sure to measure voltage (DC) on both capacitor terminals located in controller back, and check that the voltage is discharged sufficiently.(Refer to Fig.2)) Disconnect the connectors from the control PCB. Disconnect the white wiring passing through CT1 on the PCB before replacing the PCB.
  • Page 275 140VS Model FDC100VS, 125VS, Replace the PCB after elapsing 3 minutes from power OFF. (Be sure to measure voltage (DC) on both capacitor terminals located in controller back, and check that the voltage is discharged sufficiently.(Refer to Fig.2)) Disconnect the connectors from the control PCB. Disconnect the white wiring passing through CT1 on the PCB before replacing the PCB.
  • Page 276 Model FDC200VS, 240VS Replace the PCB after elapsing 3 minutes from power OFF. (Be sure to measure the voltage (DC) of two places (1.Resistor on PCB at the front of controller 2.Both capacitor terminals located in back of controller), and check that the voltage is discharged sufficiently. (Refer to Fig.2)) Disconnect the connectors from the control PCB.
  • Page 277 (c) Outdoor inverter PCB replacement procedure Model FDC71VN Replace the PCB after elapsing 3 minutes from power OFF. (Be sure to measure voltage (DC) between T26 and T27 on inverter PCB, and check that the voltage is discharged sufficiently (10V or less). (Refer to Fig.2)) Take off the connection of inverter PCB terminal and connector, and remove the screw of power transistor (IC10), active filter (IC2), and diode stack (DS1) then remove the PCB.
  • Page 278 Model FDC100VN, 125VN, 140VN Replace the PCB after elapsing 3 minutes from power OFF. (Be sure to measure voltage (DC) on both capacitor terminals located in controller back, and check that the voltage is discharged sufficiently.(Refer to Fig.2)) Take off the connection of inverter PCB terminal block connector and remove the screw of power transistor then remove the PCB.
  • Page 279 140VS Model FDC100VS, 125VS, Replace the PCB after elapsing 3 minutes from power OFF. (Be sure to measure voltage (DC) on both capacitor terminals located in controller back, and check that the voltage is discharged sufficiently.(Refer to Fig.2)) Take off the connection of inverter PCB terminal block connector and remove the screw of power transistor then remove the PCB.
  • Page 280 Model FDC200VS, 250VS Replace the inverter PCB after 10 minutes from power OFF. (Be sure to check that LED(LED1,2) of the inverter PCB put out the lights. It measures that the voltage (AC) between terminals(R,S,T) on the noise filter PCB (see Fig 2) is discharged sufficiently.) Remove the terminal on the terminal block (TB1) of the inverter PCB and the connector (CNR) of exchange the PCB.
  • Page 281 ���� ������ ������� ���� �������� ����� ��� ������� ��� Model FDC71VN Switches Description Default setting Remarks SW3-1 Defrost condition Normal*/Cold region Normal Snow protection control Normal SW3-2 Normal*/Snow protection Model selection Cooling only/Heat pump* Heat pump Keep OFF SW3-3 Defrost prohibition time ON: 37min*/OFF: 45min 37min.
  • Page 282: Check Of Anomalous Operation Data With The Remote Controller

    Check of anomalous operation data with the remote controller Operation data can be checked with remote control unit operation. Press the button. The display change “ ” Press the (SET) button while “ ” is displayed. When only one indoor unit is connected to remote controller, “...
  • Page 283 Details of Compressor protection status No. 33 263-1 – –...
  • Page 284: Inspection Display Of Wireless Specification Model (Fden,Fdt)

    Inspection display of wireless specification model (FDEN, FDT) Display FDEN Series FDT (Wireless kit) [For details of the wireless kit, refer to page 353.] – –...
  • Page 285: Power Transistor Module (Including The Driver Pcb) Inspection Procedure

    Power transistor module (including the driver PCB) inspection procedure Power transistor module terminal short circuit check procedure Disconnect the compressor wiring, then conduct a short circuit check. P-U, P-V, P-W Check for a power transistor short circuit. N-U, N-V, N-W •...
  • Page 286 •¡•@ inverter checker for diagnosis of inverter output Checking method Model: FDC71VN, 100VN, 125VN, 140VN,100VS, 125VS, 140VS, 200VS, 250VS 1) Setup procedure of checker. a) Power OFF (Turn off the breaker). b) Remove the terminal cover of compressor and disconnect the wires (U, V, W) from compressor. c) Connect the wires U (Red) , V (White) and W (Black) of checker to the terminal of disconnected wires (U, V, W) from compressor respectively.
  • Page 287: Troubleshooting Flow

    Troubleshooting flow List of troubles Remote controller display Description of trouble Reference page None Operates but does not cool. None Operates but does not heat. None Earth leakage breaker activated None Excessive noise, vibration (1/3) None Excessive noise, vibration (2/3) None Excessive noise, vibration (3/3) None...
  • Page 288 Troubleshooting Keeps flashing Stays Off None Operates but does not cool Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure It is normal. (This unit is designed to start in the soft start mode by detecting the under dome temperature of compressor when it restart after power reset.
  • Page 289 Keeps flashing Stays Off None Operates but does not heat Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure It is normal. (This unit is designed to start in the soft start mode by detecting the under dome temperature of compressor when it restart after power reset.
  • Page 290 Stays Off Stays Off None Earth leakage breaker activated Stays Off Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Replace compressor. 2. Error detection method Secure insulation resistance. 3. Condition of Error displayed 4. Presumable cause • Defective compressor •...
  • Page 291 – – None Excessive noise/vibration (1/3) – – 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure If excessive noise/vibration persists when sufficient time has elapsed after stopping the unit, it is considered that the air- conditioner is not the source.
  • Page 292 – – None Excessive noise/vibration (2/3) – – 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Rearrange the piping to avoid contact with the casing. It is noise/vibration that is generated when the 2. Error detection method refrigerant gas or liquid flow through inside of piping of air-conditioner.
  • Page 293 – – None Excessive noise/vibration (3/3) – – 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure If insufficient cooling/ heating problem happens due to anomalous operating conditions at cooling /heating, followings are 2. Error detection method suspicious. • Overcharge of refrigerant •...
  • Page 294 Keeps flashing Stays Off None Louver motor failure Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure 2. Error detection method Repair wiring. Replace indoor control PCB. Replace LM. Normal 3. Condition of Error displayed Adjust LM lever and then check again.
  • Page 295 Power supply system error Stays Off Stays Off None (Power supply to indoor unit PCB) Stays Off 2 times flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Defective outdoor PCB (Noise filter) 2. Error detection method Misconnection or breakage of connecting wires Defective indoor power Replace.
  • Page 296 Power supply system error Keeps flashing Stays Off None (Power supply to remote controller) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Correct. 2. Error detection method Replace wires. Replace remote controller. 3. Condition of Error displayed Replace power PCB.
  • Page 297 INSPECT I/U Keeps flashing Stays Off INSPECT I/U (When1 or 2 remote controllers are connected) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Set SW1 on remote controller PCB at “Master”. 2. Error detection method Communication between indoor unit and remote controller is disabled for more than 30...
  • Page 298 INSPECT I/U Keeps flashing Stays Off INSPECT I/U (connection of 3 units or more remote controller) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Reduce to 2 units or less. Change remote controller 2. Error detection method setting to “Master”.
  • Page 299 Green Content Error code (1/3) WAIT Keeps flashing Stays Off Indoor Remote controller: WAIT (Model SRC40 - 60) Outdoor Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model Model SRC40 – 60 Diagnosis Countermeasure When the remote controller LCD displays “ ”...
  • Page 300 (2/3) Keeps flashing Stays Off (Model SRC40 - 60) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model Model SRC40 – 60 Diagnosis Countermeasure When the fuse is blown, the method to inspect inverter before replacing the power supply fuse 2.
  • Page 301 Green Content Error code (3/3) WAIT Keeps flashing Stays Off Indoor Remote controller: WAIT (Model SRC40 - 60) Outdoor Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model Model SRC40 – 60 Diagnosis Countermeasure When the remote controller display is extinguished after the power on.
  • Page 302 (1/3) Keeps flashing Stays Off (Model 71 - 250) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model Model FDC71 – 250 Diagnosis Countermeasure See next page. 2. Error detection method Defective indoor control Defective indoor PCB Defective remote controller Broken remote controller wire Y Correct connection wires.
  • Page 303 (2/3) Keeps flashing Stays Off (Model 71 – 250) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model Model FDC71 - 250 Diagnosis Countermeasure 2. Error detection method Normal (Malfunction by noise) See next page. Replace noise filter. Check connection of diode stack and electrolytic 3.
  • Page 304 (3/3) Keeps flashing Stays Off (Model 71 – 250) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model Model FDC71 - 250 Diagnosis Countermeasure 2. Error detection method 3. Condition of Error displayed 4. Presumable cause • Blown fuse •...
  • Page 305 No display Keeps flashing Stays Off None (Model 71 – 250) Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model Model FDC71 - 250 Diagnosis Countermeasure Defective remote controller 2. Error detection method Defective remote controller Defective connecting wire. Defective remote controller wire (Short-circuit, etc.) Defective indoor control...
  • Page 306 Remote controller Keeps flashing Stays Off communication circuit error Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Malfunction by noise Check peripheral environment. 2. Error detection method When normal communication between the remote controller and the indoor unit is interrupted for more than 2 Defective indoor PCB minutes.
  • Page 307 Keeps flashing See below Communication error during operation Keeps flashing 2 times flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Repair signal wires. 2. Error detection method When normal communication Repair signal wires. between indoor and outdoor unit is interrupted for more than 2 minutes.
  • Page 308 Indoor heat exchanger Keeps flashing 1 time flash temperature thermistor anomaly Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Correct. Insert connector securely. 2. Error detection method Defective indoor heat exchanger temperature Anomalously low temperature thermistor Replace.
  • Page 309 Return air temperature Keeps flashing 1 time flash thermistor anomaly Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Correct. Connect connector. 2. Error detection method Defective return air temperature thermistor Anomalously low temperature Replace. or high temperature (resistance) is detected by indoor return air temperature thermistor (Thi-A) Defective indoor control...
  • Page 310 Keeps flashing 1 time flash Heating overload operation Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Wash. 2. Error detection method Defective indoor heat exchanger temperature thermistor connector Indoor heat exchanger Correct. temperature thermistor (ThI-R1, R2, R3) Defective indoor heat exchanger temperature...
  • Page 311 Drain trouble Keeps flashing 1 time flash (FDT and FDTC Series) Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model FDT and FDTC Series only Diagnosis Countermeasure Check float switch. 2. Error detection method Float switch is activated Replace indoor control PCB.
  • Page 312 Excessive number of connected indoor units (more than 17 units) Keeps flashing Stays Off by controlling with one remoto controller Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Defective remote controller Replace. Reduce to 16 or less units. 2.
  • Page 313: Communication Error

    Communication error Keeps flashing 1 time flash between master and slave indoor units Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Correct unit address setting. Correct wiring. 2. Error detection method When communication error between master and slave indoor units occurs Defective indoor control PCB Replace.
  • Page 314 Indoor fan motor anomaly Keeps flashing Stays Off (In case of FDTC and FDT) Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model FDTC, FDT series only Diagnosis Countermeasure Remove foreign material. 2. Error detection method Replace the fan motor. Detected by rotation speed of indoor fan motor Check power voltage.
  • Page 315 Indoor unit operation check, Keeps flashing 1 time flash drain motor check setting error Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Defective indoor control PCB (Defective SW7) Replace 2. Error detection method Turn SW7-1 on the indoor After indoor operation check, control PCB OFF and reset when the communication...
  • Page 316 Remote controller Keeps flashing Stays Off temperature thermistor anomaly Keeps flashing Stays Off 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure 2. Error detection method Correct. Detection of anomalously low temperature (resistance) of remote controller temperature thermistor (Thc) Defective remote controller temperature thermistor Replace.
  • Page 317 Inverter primary current error Keeps flashing – (Model SRC40 – 60) – 8 times flash 5. Troubleshooting 1. Applicable model SRC40 – 60 types Diagnosis Countermeasure Restore normal condition. 2. Error detection method Restore normal condition. Inverter primary current Remove foreign matter like dust, fouling, etc.
  • Page 318 Delete Delete Delete Delete – 297 –...
  • Page 319 Delete Delete Delete Delete – 298 –...
  • Page 320 Cooling overload operation Keeps flashing Stays Off (Model SRC40 - 60 only) – 8 times flash 5. Troubleshooting 1. Applicable model Model SRC40 – 60 Diagnosis Countermeasure Replace outdoor heat exchanger temperature thermistor. 2. Error detection method Check unit side. •...
  • Page 321 Cooling overload operation Keeps flashing Stays Off (Model FDC71 - 250 only) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model Model FDC71 – 250 Diagnosis Countermeasure Replace outdoor heat exchanger temperature thermistor. 2. Error detection method Check unit side. •...
  • Page 322 Keeps flashing Stays Off Discharge pipe temperature error Keeps flashing 1(8) time flash Note (1) ( ) is for model 40~60. 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Replace discharge pipe temperature thermistor. 2. Error detection method Insufficient refrigerant amount : Recharge refrigerant by weighing For the error detection method,...
  • Page 323 Outdoor heat exchanger Keeps flashing Stays Off temperature themistor anomaly Keeps flashing 1(8) time flash Note (1) ( ) is for model 40~60. 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Correct connector. 2. Error detection method Detection of anomalously low temperature (resistance) on the outdoor heat exchanger Defective outdoor heat...
  • Page 324 Ambient air temperature Keeps flashing Stays Off thermistor anomaly Keeps flashing 1(8) time flash Note (1) ( ) is for model 40~60. 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Correct connector. Defective ambient air 2. Error detection method temperature thermistor Replace.
  • Page 325 Discharge pipe Keeps flashing Stays Off temperature thermistor anomaly Keeps flashing 1(8) time flash Note (1) ( ) is for model 40~60. 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Correct connector. 2. Error detection method Detection of anomalously low Defective discharge pipe temperature (resistance) on temperature thermistor...
  • Page 326 High pressure error (63H1 activated) Keeps flashing Stays Off (Model FDC71 - 250) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model Model FDC 71 – 250 Diagnosis Countermeasure Open service valve. 2. Error detection method When the high pressure switch 63H1 is activated.
  • Page 327 Green Error code Error code Content Stays Indoor control PCB Keeps flashing Remote controller: E41 Power transistor overheat 1 time Outdoor control PCB Keeps flashing (1/2) flash Red LED Green (Model FDC200, 250 only) Outdoor inverter 6 times flash or Keeps 2 times flash flashing...
  • Page 328 Green Error code Error code Content Stays Indoor control PCB Keeps flashing Remote controller: E41 1 time Power transistor overheat (2/2) Outdoor control PCB Keeps flashing flash (Model FDC71-140 only) Yellow LED Outdoor inverter PCB 6 times flash or 2 times flash 1.
  • Page 329 Keeps flashing Stays Off Current cut (1/2) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Check power supply. 2. Error detection method Open the valves. In order to prevent from overcurrent of inverter, Check refrigerant amount if the current exceeds the and refregerant circuit specifications, it makes the...
  • Page 330 Keeps flashing Stays Off Current cut (2/2) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Replace inverter PCB 2. Error detection method In order to prevent from overcurrent of inverter, if the current exceeds the specifications, it makes the compressor stopping.
  • Page 331 Green Content Error code Error code Keeps stays Communication error between Indoor flashing Remote Controller: E45 inverter PCB and outdoor control PCB Keeps 1 time Outdoor (Model FDC71-140 and 200, 250) flashing flash 1. Applicable Model 5. Troubleshooting Diagnosis Countermeasure FDC71-140VN inverter PAC models FDC100-140VS inverter PAC models FDC200, 250VS inverter PAC model...
  • Page 332 Inverter over-current error Keeps flashing Stays Off (Model SRC40 – 60) – 1 time flash 5. Troubleshooting 1. Applicable model Model SRC40 – 60 Diagnosis Countermeasure Remove foreign matter like dust, fouling, etc. 2. Error detection method Replace fuse. Error is displayed if the converter voltage exceeds 340V (3 times within 20 minutes).
  • Page 333 Outdoor DC fan motor error Keeps flashing Stays Off (Model SRC40 - 60) – Keeps flashing 5. Troubleshooting 1. Applicable model Model SRC 40 – 60 Diagnosis Countermeasure Remove foreign matter. 2. Error detection method Replace fan motor. If resistance between (Vm):red - (GND):blue is Detected by rotation speed of detected 1kΩ...
  • Page 334 Outdoor DC fan motor error Keeps flashing Stays Off (Model FDC71 - 250) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model Model FDC 71 – 250 Diagnosis Countermeasure Remove foreign material. 2. Error detection method Replace fan motor. If resistance between (Vm):red - (GND):blue is Detected by rotation speed of...
  • Page 335 Low pressure error or low pressure sensor anomaly (1/2) Keeps flashing Stays Off (Model FDC71 - 250) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model Model FDC 71 – 250 Diagnosis Countermeasure Correct. 2. Error detection method Detected by low pressure drop and suction superheat 3.
  • Page 336 Low pressure error or low pressure sensor anomaly (2/2) Keeps flashing Stays Off (Model FDC71 - 250) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model Model FDC 71 – 250 Diagnosis Countermeasure 2. Error detection method Open fully. Correct.
  • Page 337 Green Error code Error code Content Stays Keeps flashing Indoor control PCB Remote Controller: E51 Inverter anomaly (1/2) 1 time Keeps flashing Outdoor control PCB (Model FDC71-140 only) flash Yellow LED Outdoor inverter 6 times flash or 2 times flash 1.
  • Page 338 Green Error code Error code Content Stays Indoor control PCB Keeps flashing Remote Controller: E51 Inverter anomaly (2/2) 1 time Outdoor control PCB Keeps flashing (Model FDC200, 250 only) flash Red LED Green Outdoor inverter PCB 6 times flash or Keeps 2 times flash flashing...
  • Page 339 Suction pipe temperature thermistor anomaly Keeps flashing Stays Off (Model FDC71 - 250) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model Model FDC 71 – 250 Diagnosis Countermeasure 2. Error detection method Correct connection of suction pipe temperature When the suction pipe thermistor connector.
  • Page 340 Low pressure sensor anomaly Keeps flashing Stays Off (Model FDC71 - 250) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model Model FDC 71 – 250 Diagnosis Countermeasure Correct low pressure sensor connector connection. 2. Error detection method Is refrigerant amount charged properly? When anomalous voltage Is there any anomaly on the...
  • Page 341 Underneath temperature thermistor anomaly Keeps flashing Stays Off (Model FDC200, 250) Keeps flashing 1 time flash 5. Troubleshooting 1. Applicable model FDC 200, 250 types Diagnosis Countermeasure Correct connection of underneath temperature thermistor connector. 2. Error detection method Defective underneath temperature thermistor When anoumalous low Replace.
  • Page 342 Insufficient refrigerant amount Keeps flashing Stays Off or detection of service valve closure Keeps flashing 1(2) time flash Note (1) ( ) is for model 40~60. 5. Troubleshooting 1. Applicable model All models Diagnosis Countermeasure Open fully. Correct indoor heat 2.
  • Page 343 Compressor startup failure Keeps flashing Stays Off (Model SRC40~60) – 2 times flash 5. Troubleshooting 1. Applicable model Model SRC40~60 Diagnosis Countermeasure Replace outdoor fan motor 2. Error detection method Check power supply voltage If it fails to change over to the rotor detection operation of compressor motor (If the compressor speed cannot...
  • Page 344 Error code Error code Content Compressor startup failure (1/2) ( Model FDC71-140 and 200,250 ) FDC71-140VN inverter PAC models FDC100-140VS inverter PAC models FDC200, 250VS inverter PAC models When it fails to change over to the operation for rotor position detection of compressor motor (If the compressor speed cannot increase 11Hz or higher) If the compressor fails to startup for...
  • Page 345 Green Error code Error code Content Stays Indoor control PCB Keeps flashing Remote Controller: E59 Compressor startup failure (2/2) 1 time Outdoor control PCB Keeps flashing flash ( Model FDC71-140 and 200,250 ) Yellow LED (Red for 200, 250VS) Outdoor inverter Stays off or 4 times flash 1.
  • Page 346 Compressor rotor lock error Keeps flashing Stays Off (Model SRC40~60, FDC200, 250) Keeps flashing 1(7) time flash Note (1) ( ) is for model 40~60. 5. Troubleshooting 1. Applicable model Model SRC40~60, FDC 200, Diagnosis Countermeasure Check and correct the power supply voltage 2.
  • Page 347 2. MULTI-TYPE (V MULTI) PACKAGED AIR-CONDITIONER CONTENTS 2.1 GENERAL INFORMATION ..................324 2 2 .1.1 Specific features ....................3 3 24 2.1.2 How to read the model name ................3 3 24 2.1.3 Table of models....................3 3 25 2.1.4 Table of system combinations................3 3 25 2.2 SELECTION DATA ....................
  • Page 348 Ideal for the installation in Large, single zone open Areas and L-shaped rooms, the Muliti-Type V series allows an extensive degree of flexibility in the selection of indoor units. Specifically, the selection of indoor units with differing capacities and differing or similar types is available, as is the selection of indoor units with similar capacities and differing types.
  • Page 349 2.1.3 Table of models Capacity Model Ceiling cassette-4way Compact (600 x 600mm)-type (FDTC) Ceiling cassette-4way-type (FDT) Ceiling suspended type (FDEN) Duct connected-Middle static pressure-type (FDUM) FDC71VN FDC125VN FDC140VN FDC200VS FDC250VS (3 Horse Power) FDC125VS FDC140VS (8 Horse Power) (10 Horse Power) Outdoor unit to be combined (FDC) FDC100VN (5 Horse Power)
  • Page 350 Noise level dB(A) Hi: 42 Me : 38 Lo: 35 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Turbo fan 1 Fan type & Q'ty Starting method Direct line start Outside air intake Not possible Air filter, Q'ty Pocket plastic net...
  • Page 351 Noise level dB(A) Hi: 33 Me : 31 Lo: 30 Hi: 33 Me : 31 Lo: 30 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Turbo fan 1 Fan type & Q'ty Starting method Direct line start Outside air intake Possible...
  • Page 352 Noise level dB(A) Hi: 35 Me: 33 Lo: 31 Hi: 40 Me: 37 Lo: 35 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Turbo fan 1 Fan type & Q'ty Starting method Direct line start Outside air intake Possible Air filter, Q'ty...
  • Page 353 Noise level dB(A) Hi: 42 Me: 40 Lo: 37 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Turbo fan 1 Fan type & Q'ty Starting method Direct line start Outside air intake Possible Air filter, Q'ty Pocket plastic net 1 (Washable)
  • Page 354 Noise level dB(A) Hi: 39 Me : 38 Lo: 37 Hi: 41 Me : 39 Lo: 38 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Centrifugal fan 2 Centrifugal fan 4 Fan type & Q'ty Starting method Direct line start Outside air intake...
  • Page 355 Noise level dB(A) Hi: 41 Me: 39 Lo: 38 Hi: 44 Me: 41 Lo: 39 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Centrifugal fan 4 Fan type & Q'ty Starting method Direct line start Outside air intake Not possible Pocket plastic net...
  • Page 356 Noise level dB(A) Hi: 46 Me: 44 Lo: 43 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Centrifugal fan 4 Fan type & Q'ty Starting method Direct line start Outside air intake Not possible Air filter, Q'ty Pocket plastic net 2 (Washable)
  • Page 357 Noise level dB(A) Hi: 34 Me: 31 Lo: 28 Hi: 35 Me: 32 Lo: 29 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Centrifugal fan 2 Fan type & Q'ty Starting method Direct line start Outside air intake Possible Air filter, Q'ty...
  • Page 358 Noise level dB(A) Hi: 37 Me: 35 Lo: 32 Hi: 38 Me: 36 Lo: 33 Refrigerant equipment Louver fin & inner grooved tubing Heat exchanger Refrigerant control Air handling equipment Centrifugal fan 3 Fan type & Q'ty Starting method Direct line start Outside air intake Possible Air filter, Q'ty...
  • Page 359 Noise level dB(A) Refrigerant equipment 2YC45DXD 1 compressor type & Q' ty Starting method Direct line start Crankcase heater Straight fin & inner grooved tubing Heat exchanger Refrigerant control Electronic expansion valve Defrost control Microcomputer controlled de-icer Air handling equipment Propeller fan 1 Fan type &...
  • Page 360 Noise level dB(A) Refrigerant equipment RMT5126MDE2 1 compressor type & Q' ty Starting method Direct line start Crankcase heater Straight fin & inner grooved tubing Heat exchanger Refrigerant control Electronic expansion valve Defrost control Microcomputer controlled de-icer Air handling equipment Propeller fan 1 Fan type &...
  • Page 361 Noise level dB(A) Refrigerant equipment RMT5126MDE3 1 compressor type & Q' ty Starting method Direct line start Crankcase heater Straight fin & inner grooved tubing Heat exchanger Refrigerant control Electronic expansion valve Defrost control Microcomputer controlled de-icer Air handling equipment Propeller fan 1 Fan type &...
  • Page 362 Noise level dB(A) Cooling: 50, Heating: 51 Refrigerant equipment RMT5126MDE2 1 compressor type & Q' ty Starting method Direct line start Crankcase heater Heat exchanger Straight fin & inner grooved tubing Refrigerant control Electronic expansion valve Defrost control Microcomputer controlled de-icer Air handling equipment Propeller fan 1 Fan type &...
  • Page 363 Noise level dB(A) Cooling: 50, Heating: 51 Refrigerant equipment RMT5126MDE2 1 compressor type & Q' ty Starting method Direct line start Crankcase heater Heat exchanger Straight fin & inner grooved tubing Refrigerant control Electronic expansion valve Defrost control Microcomputer controlled de-icer Air handling equipment Propeller fan 1 Fan type &...
  • Page 364 Noise level dB(A) Cooling: 57, Heating: 58 Refrigerant equipment GTC5150ND70K 1 compressor type & Q' ty Starting method Direct line start Crankcase heater Straight fin & inner grooved tubing Heat exchanger Refrigerant control Electronic expansion valve Defrost control Microcomputer controlled de-icer Air handling equipment Propeller fan 2 Fan type &...
  • Page 365 The Multi-Type V series is a system that allows for different models and capacities of indoor units to be connected so the individual operating characteristics of the indoor and outdoor are provided. Use the procedure shown in Item (c) to calculate the combined operating characteristics.
  • Page 366 (220-240V 50Hz/220V 60Hz) Cooling power consumption 0.14-0.16/0.14 0.15-0.17/0.15 0.16-0.19/0.16 0.24-0.28/0.24 0.28-0.32/0.32 Heating power consumption 0.14-0.16/0.14 0.15-0.17/0.15 0.16-0.19/0.16 0.24-0.28/0.24 0.28-0.32/0.32 Cooling running current 0.63-0.67/0.63 0.68-0.71/0.68 0.73-0.79/0.73 1.07-1.17/1.07 1.28-1.32/1.28 Heating running current 0.63-0.67/0.63 0.68-0.71/0.68 0.73-0.79/0.73 1.07-1.17/1.07 1.28-1.32/1.28 Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”...
  • Page 367 Total power factor (%) × 100 . = . 99 % 4.71 × 1000 (Cooling) 21.0 × 220 4.60 × 1000 × 100 . = . 99 % (Heating) 20.1 × 220 Total power consumption (kW) = Power consumption of outdoor unit + ∑ (Power consumption of indoor unit) Total running current (A) = Running current of outdoor unit + [∑...
  • Page 368: Range Of Usage & Limitations

    2.2.2 Range of usage & limitations See the next page. When used below -5 , install a snow hood(option). Considering to get sufficient heating capacity, the area where the averaged lowest ambient air temperature in day time during winter is above 0 , and it has no accumulation of snow.
  • Page 369 Operating temperature range Models 40 Cooling Usage range in cooling Indoor air temperature Heating Usage range in heating Outdoor air temperature Decline in cooling and heating capacity or operation stop may occur when the outdoor unit is installed in places where natural wind can increase or decrease its design airflow rate. PCA001Z561 “CAUTION”...
  • Page 370 PCA001Z561...
  • Page 371 PCA001Z561 346-1...
  • Page 372: Exterior Dimensions

    2.2.3 Exterior dimensions Details are the same as in chapter 1.2.3 see page 90. 2.2.4 Exterior appearance Details are the same as in chapter 1.2.4 see page 109. 2.2.5 Piping system Details are the same as in chapter 1.2.5 see page 111. 2.2.6 Selection chart Details are the same as in chapter 1.2.6 see page 118.
  • Page 373: Application Date

    2.5 APPLICATION DATE Except below mentioned items, see chapter 1.5 in page 178. INSTRUCTIONS FOR BRANCHING PIPE SET INSTALLATION FOR TWIN/TRIPLE/ W-TWIN CONFIGURATION SYSTEMS For R410A PSB012D865 WARNING / CAUTION This set is for R410A refrigerant. Select a branching pipe set correctly rated for the combined total capacity of connected indoor units and install it according to this manual. An improperly installed branching pipe set can cause degraded performance or an abnormal unit stop.
  • Page 374 2. Pipe connecting procedure Braze the different diameter pipe joint found in the set matching the connected outdoor and indoor unit capacities according to the instructions set out below. In connecting an indoor unit of which capacity is 1.5HP, 2HP or 2.5HP always use a 9.52 liquid pipe to connect to the branching CAUTION pipe (branching pipe - indoor unit).
  • Page 375 2-5 Triple type for same model/same capacity or different model/same capacity When the difference in length of pipes after the branch is longer than 3 m and shorter than 10 m. Outdoor unit model Indoor unit model Branching pipe Branching pipe set type Liquid branching pipe Gas branching pipe Flare joint...
  • Page 376: Maintenance Date

    2-7. W-twin type Pipes should be connected as follows for a W-twin installation (4 connected indoor units. The capacity of an outdoor unit availble for this configuration is either 8HP or 10HP only): Branching pipe Outdoor unit model Liquid branching pipe Gas branching pipe Outdoor unit capacity Indoor unit capacity...
  • Page 377 3. WIRELES KIT (OPTIONAL PARTS) 3.1 FDT SERIES (RCN-T-36W-E) ..............353 3.2 FDTC SERIES (RCN-TC-24W-ER) ............359 3.3 EXCEPT FOR FDT AND FDTC SERIES (RCN-KIT3-E) ..... 365 WARNING ¡ Fasten the wiring to the terminal securely and hold the cable securely so as not to apply unexpected stress on the terminal.
  • Page 378 3.1 FDT SERIES The FDT series is an exclusive series with all wired models. However, these models can also be used wireless units by using the optional wireless kit. Wireless kit model Model RCN-T-36-W-E (2) Accessories Please make sure that you have all of the following accessories. Receiver Remote controller holder Wireless...
  • Page 379 Remove the cover by unscrewing two screws from the back of receiver. Change the setting by the switch on PCB. Screws Default settings Switch Receiver Backside Cover Backside When SW1 is turned to OFF position, change the corresponding remote controller setting as follows: How to change the remote controller setting Pressing ACL and AIR FLOW button at the same time or inserting the batteries with pressing AIR FLOW button will customize the signal.
  • Page 380 Installation of the receiver Loosen the bolts which fix the panel and make a gap between the panel and the indoor unit Put the wiring of the receiver through the opening. Put the wiring on the notch on the control box so as not to be pinched by the control box and lid as shown below. Connect the wiring to the terminal block provided in the control box.
  • Page 381 (4) Remote controller Installation of the controller holder Caution DO NOT install it on the following places 1. Places exposed to direct sunlight 2. Places near heat devices 3. High humidity places 4. Hot surface or cold surface enough to generate condensation 5.
  • Page 382 Control plural indoor units with one remote controller Up to 16 indoor units can be connected. Connect the XY terminal with 2-core wire. As for the size, refer to the following note. For Packaged air conditioner series, set the indoor unit address with SW2 on the indoor unit PCB from [0] to [F] so as not to duplicate.
  • Page 383 Correlation between illuminance at the receiver and The receivable area of the signal when the illuminance reachable area of the signal in a plain view. The draw- at the receiver is 300lux ing in the right shows the correlation between the reachable area of the signal and illuminance at the receiver when the remote controller is operated at 1.1m high under the condition of ceiling height of...
  • Page 384: Fdtc Series

    3.2 FDTC SERIES The FDTC series is an exclusive series with all wired models. However, these models can also be used wireless units by using the optional wireless kit. Wireless kit model Model RCN-TC-24W-ER (2) Accessories Please make sure that you have all of the following accessories. Receiver Remote controller holder Wireless...
  • Page 385 Setting on site PCB on the receiver has the following switches to set the functions. Default setting is shown with mark. Customized signal setting to avoid Normal mixed communication Remote Master Receiver master/slave setting Slave Valid Buzzer valid/Invalid Invalid Valid Auto restart Invalid Remove the cover by unscrewing two screws from the back of receiver.
  • Page 386 Installation of the receiver Attach the receiver to the panel according to the panel installation manual. Remove two screws and detach the lid from the control box. Put the wiring in the control box with other wiring as shown below. Connect the wiring to the terminal block (X, Y) provided in the control box.
  • Page 387 Remote controller Installation of the controller holder Caution Do not install it on the following places 1. Places exposed to direct sunlight 2. Places near heat devices 3. High humidity places 4. Hot surface or cold surface enough to generate condensation 5.
  • Page 388 Control plural indoor units with one remote controller Up to 16 indoor units can be connected. Connect the XY terminal with 2-core wire. As for the size, refer to the following note. For signal packaged air conditioner series, set the indoor unit address with SW2 on the indoor unit PCB from [0] to [F] so as not to duplicate.
  • Page 389 The receivable area of the Correlation between illuminance at the receiver and signal when the illuminance at the receiver is 300lux reachable area of the signal in a plain view. The draw- ing in the right shows the correlation between the reachable area of the signal and illuminance at the receiver when the remote controller is operated at 1m high under the condition of ceiling height of 2.4m.
  • Page 390 3.3 EXCEPT FOR FDT & FDTC SERIES This product is dedicated for heat pump unit. Never install on the unit dedicated for cooling. Wireless kit model Model RCN-KIT3-E (2) Accessories (Confirm the following accessories). Remote controller Light detection holder adaptor Screw for holder Wiring (3m) AAA dry...
  • Page 391 How to install the receiver The following two methods can be used to install the receiver onto a ceiling or a wall. Select a method according to the installation position. <Installation position> Direct installation onto the ceiling with wood screws. Installation with accessory's bracket Drilling of the ceiling (ceiling opening) Drill the receiver installation holes with the following dimensions at the ceiling position where wires can be connected.
  • Page 392 1 Put through the wiring from the back side to the hole of the lower case. 2 Fit the lower case into the ceiling opening. Make sure that the clearance between the convex part of the back of the lower case and the ceiling opening must be as equal as possible on both sides.
  • Page 393 Remote controller Installation of the controller holder Caution Do not install it on the following places Holder for 1. Places exposed to direct sunlight remote controller 2. Places near heat devices 3. High humidity places 4. Hot surface or cold surface enough to generate condensation 5.
  • Page 394 Setting of wireless remote controller and receiver (A) Methods of avoiding the malfunction due to the mixed communication Do both procedures 1 and 2. This setting is to avoid the mixed communication with other household electric appliances or the mixed communication when two receivers are located closely.
  • Page 395 (B) Control plural indoor units with one remote controller Up to 16 indoor units can be connected. Connect the XY terminal with 2-core wire. As for Restrictions on the thickness and length of wire the size, refer to the following note. (Maximun total extension 600m.) Standard Within 100m x 0.3 mm...

Table of Contents